82
Spare Part:
R7910
Repair Control Kit
P/N 106177-01
Maximum
Light-off Heat Rate
= 4000
R7910
Repair Control Kit
P/N 106177-02
Maximum
Light-off Heat Rate
= 3000
R7910
Repair Control Kit
P/N 106177-03
Maximum
Light-off Heat Rate
= 2500 rpm
Altitude
0 - 7000 Ft.
7001 - 10,000 Ft.
Boiler Type
210
-02
210
-27
285
-07
210
-70
285
-70
Minimum Heat Rate
1370
2400
1450
1800
2400
Maximum Heat Rate
5950
5950
5560
7000
7000
Absolute
Maximum Heat Rate
6350
6350
6200
7000
7000
Light-off Heat Rate
4000
3000
2500
X. Operation
F. Changing Adjustable Parameters (continued)
WARNING
Asphyxiation Hazard. Boiler type is factory set and must match the boiler model. Only change the boiler
type setting if you are installing a new or replacement Control. The boiler type setting determines minimum
and maximum blower speeds. Incorrect boiler type can cause hazardous burner conditions and improper
operation that may result in PROPERTY LOSS, PHYSICAL INJURY OR DEATH.
Table 29: Parameters Changed Using the Boiler Type Parameter Selections:
NOTE:
Maximum Modulation Rates are designed for 100% nameplate rate at 0°F (-18°C) combustion air.
Contact factory before attempting to increase the Maximum Modulation Rate.
“Press”
Modulation
Setup
button to access the following parameters:
Factory
Setting
Range / Choices
Parameter and Description
See Table
29
See Table 29
Boiler Type
Boiler Size Setup
To verify the boiler size selection, a qualified technician should do the following:
1. Check boiler’s label for actual boiler size.
2. Set “Boiler Type” to match actual boiler size.
3. Select “Confirm”.
The Boiler Type parameter changes the minimum and maximum modulation settings. This param
-
eter is intended to allow a user to set the parameters in a spare part Control to a particular boiler
type.
Summary of Contents for Phantom-X PHNTM210
Page 7: ...7 Figure 1B Model PHNTM285 I Product Description Specifications and Dimensional Data continued...
Page 52: ...52 VIII Electrical continued...
Page 53: ...53 VIII Electrical continued Figure 26 Wiring Connections Diagram...
Page 54: ...54 VIII Electrical continued Figure 27 Ladder Diagram...
Page 118: ...118...
Page 119: ...119...