15
Table 4: Vent/Combustion Air System Options
IV. Venting
A. General Guidelines (continued)
Approved Direct
Vent System
Vent
Material
Orientation
Termination
Description
Figures
Compo-
nent
Table
Part
Factory Standard
Two-Pipe,
CPVC/PVC Vent and
PVC Air Intake
CPVC/PVC
Horizontal
Standard
(through sidewall)
The system includes separate CPVC vent
pipe and PVC air intake pipe terminating
through sidewall with individual penetrations
for the vent and air intake piping and
separate terminals (tees).
4, 5, 6A, 6B,
9 through 13
7A
B.
Optional
Snorkel
(through sidewall)
Same as above but separate snorkel type
terminals.
4, 6A, 6B
9 through 13
7B
Optional
Vertical
Vertical
(through roof)
The system includes separate CPVC vent
pipe and PVC air intake pipe terminating
through roof with individual penetrations for
the vent and air intake piping and separate
vertical terminals.
7 through 11
13
7C
Available Optional
Two-Pipe, Rigid
Polypropylene Vent (or
Flexible Polypropylene
Liner for Vertical
venting only) and Rigid
Polypropylene or PVC
Pipe Air Intake
Rigid
Polypropylene
(or Flexible
Polypropylene
Liner for vertical
Venting only)
Horizontal
Standard
(through sidewall)
The system includes separate Rigid
Polypropylene vent pipe and Rigid
Polypropylene or PVC air intake pipe
terminating through sidewall with individual
penetrations for the vent and air intake
piping and separate terminals (tees).
4, 5, 6A, 6B
9, 12, 14
10A, 10B
C.
Optional Snorkel
(through sidewall)
Same as above but separate snorkel type
terminals.
4, 6A, 6B
9, 12, 14
10A, 10B
Optional
Vertical
Vertical
(through roof or
chimney/chase)
The system includes separate Flexible
Polypropylene vent liner and Rigid
Polypropylene vent pipe combination for
venting and Rigid Polypropylene or PVC
air intake pipe terminating through roof with
individual penetrations for the vent and air
intake and separate terminals.
7 through 9
14, 15
10A, 10B
Available Optional
Two-Pipe,
Stainless Steel Vent and
PVC/Galvanized Steel
Air Intake
Stainless Steel
Horizontal
Standard
(through sidewall)
The system includes separate stainless
steel vent pipe and PVC/galvanized steel
air intake pipe terminating through sidewall
with individual penetrations for the vent and
air intake piping and separate terminals.
4, 5, 6A, 6B
9, 12, 16
11A, 11B
D.
Optional Snorkel
(through sidewall) Same as above but separate snorkel type
terminals.
4, 6A, 6B
9, 12, 16
Optional
Vertical
Vertical
(through roof or
chimney/chase)
The system includes separate Flexible
stainless steel vent liner and Rigid stainless
steel vent pipe and PVC/galvanized steel
air intake pipe terminating through roof with
individual penetrations for the vent and air
intake piping and separate terminals.
7 through 9
17, 17A
Table 5: Vent/Combustion Air Pipe Length – Two-Pipe Direct Vent System Options
• CPVC/PVC
• Polypropylene (PP) or Polypropylene (PP)/PVC
• Stainless Steel/PVC or Galvanized Steel
Boiler Model
Combustion Air
Vent
Nominal
Pipe
Diameter
Minimum
Equivalent
Length
Maximum
Equivalent
Length
Nominal
Pipe
Diameter
Minimum
Equivalent
Length
Maximum
Equivalent
Length
PHNTM210
4 in.
(100 mm or 110 mm)
2.5 ft.
(760 mm)
135 ft.
(41.1)
3 in.
(80 mm)
2.5 ft.
(760 mm)
135 ft.
(41.1)
PHNTM285
100 ft.
(30.5 m)
4 in.
(100 mm or 110 mm)
100 ft.
(30.5 m)
Summary of Contents for Phantom-X PHNTM210
Page 7: ...7 Figure 1B Model PHNTM285 I Product Description Specifications and Dimensional Data continued...
Page 52: ...52 VIII Electrical continued...
Page 53: ...53 VIII Electrical continued Figure 26 Wiring Connections Diagram...
Page 54: ...54 VIII Electrical continued Figure 27 Ladder Diagram...
Page 118: ...118...
Page 119: ...119...