96
“Press”
Sequence
Slave
button to access the following parameters:
Factory
Setting Range / Choices Parameter and Description
None
1-8
Boiler Address
Each boiler must be given a unique address. When ”Normal” slave selection order is used, the
boiler address is used by the Master Sequencer as the boiler start order. The boiler address is
also the Modbus Address when a Energy Management System is connected.
Normal
Use Boiler First,
Normal,
Use Boiler Last
Slave Selection Order
“Use Boiler First”; places the Slave in the lead permanently.
”Normal”; firing order follows boiler number (1,2,3,..) order.
”Use Boiler Last”; places the slave last in the firing order.
X. Operation
F. Changing Adjustable Parameters (continued)
“Press”
button to access the following parameters:
Factory Setting
Range / Choices
Parameter and Description
Central Heat 1
User defined
Zone Control 1
Zone 1
Central Heat 2
User defined
Zone Control 1
Zone 2
Central Heat 3
User defined
Zone Control 1
Zone 3
Central Heat 4
User defined
Zone Control 1
Zone 4
Central Heat 1
User defined
Zone Control 2
Zone 1
Central Heat 2
User defined
Zone Control 2
Zone 2
Central Heat 3
User defined
Zone Control 2
Zone 3
Central Heat 4
User defined
Zone Control 2
Zone 4
Central Heat 1
User defined
Zone Control 3
Zone 1
Central Heat 2
User defined
Zone Control 3
Zone 2
Central Heat 3
User defined
Zone Control 3
Zone 3
Central Heat 4
User defined
Zone Control 3
Zone 4
Central Heat 1
User defined
Zone Control 4
Zone 1
Central Heat 2
User defined
Zone Control 4
Zone 2
Central Heat 3
User defined
Zone Control 4
Zone 3
Central Heat 4
User defined
Zone Control 4
Zone 4
Use Up and DOWN Arrows for More
Exit Screen without Saving
Clear Entire Field
Backspace
Save Field and Exit
NOTE
Zone Control Description
Setup shown for 2 panels,
typical for up to 4.
Summary of Contents for Phantom-X PHNTM210
Page 7: ...7 Figure 1B Model PHNTM285 I Product Description Specifications and Dimensional Data continued...
Page 52: ...52 VIII Electrical continued...
Page 53: ...53 VIII Electrical continued Figure 26 Wiring Connections Diagram...
Page 54: ...54 VIII Electrical continued Figure 27 Ladder Diagram...
Page 118: ...118...
Page 119: ...119...