thecrowgroup.com
Page | 59
Timers
Parameter
Description
Default Configuration
Radio Zone Supervised Time
(minutes)
If a radio detector is capable of sending regular supervisory
signals to the panel and the zone type is set for 'Supervised
Signal Active', this timer sets how long a period has to
elapse with no received transmissions before a supervisory
failure alarm is generated. The time range is 1-255 minutes.
63
Two Trigger Time (seconds)
If a zone is set to two trigger, the zone has to cause an alarm
twice within the two trigger time period to cause an alarm.
If multiple zones are set to two trigger, an alarm will be
generated it two zones trigger once each within the two
trigger time period. If a two trigger zone goes into alarm
but remains in alarm for longer than the two trigger time
period (ie detector failure or cable cut) an alarm will be
generated. The time range is 5-255 seconds.
20
Delays
Parameter
Description
Default Configuration
Alarm Reporting Delay
(seconds)
If this address is set to 0, there will be no report delay. If it
is set to any value other than 0 then a delay equal to the
programmed value will stop the panel from reporting an
alarm until this delay time expires. While the timer is active
certain outputs can be disabled. Once the timer has expired
it will not start again, the panel must be disarmed then
armed to reset the timer. The value in seconds, maximal
limit is 255 seconds.
0
Mains Fail Reporting Delay
(seconds)
If a Mains Failure occurs this timer delays the reporting of
Mains Failure to a Monitoring Station. If the mains power
returns before the timer expires, then no report is sent. If
Mains Failure is assigned to an output, this delay must
expire before the output will turn on. The value in seconds,
maximal limit is 3 hours (10800 seconds).
900
Communication Fail
Reporting Delay (seconds)
If a Communication Fail occurs this timer delays the
reporting of Communication Fail to a Monitoring Station. If
specified communication path returns before the timer
expires, then no report is sent. If Communication Fail is
assigned to an output, this delay must expire before the
output will turn on. The value in seconds, maximal limit is 3
hours (10800 seconds).
0