R e p l a c i n g F u s e s
1
Disconnect and lockout the main power supply.
2
Open the electrical enclosure door.
3
Check the fuse with an ohmmeter.
If necessary, pull the fuse out and replace it with a
fuse of the same type and rating.
Fuse Blocks
To locate the appropriate fuse
and replacement part, refer to
the wiring diagrams that came
with your dryer.
IMPORTANT
: Always refer
to the wiring diagrams that
came with your dryer to lo-
cate specific electrical com-
ponents. Illustrations in the
User Guide are intended to
be representative only.
6 - 3 0
l Tr o u b l e s h o o t i n g
OFF
O
ON
I
IMPORTANT:
Always refer
to the wiring diagrams
that came with your dryer
to locate specific electri-
cal components. Illustra-
tions in the User Guide are
intended to be representa-
tive only.
OFF
O
ON
I
C h e c k i n g o r R e p l a c i n g Te m p e r a t u r e
S e n s o r s
The Carousel Plus D Series Dryer uses RTD sensors to monitor the temperatures of the return
air, the regeneration outlet, and the regeneration inlet. Your dryer may have (optional) a sen-
sor for delivery air, process protection, and/or setback.
To check or replace an RTD sensors:
1
Disconnect and lockout the main power supply.
2
Remove dryer panels, as necessary.
3
Locate the RTD sensors.
4
Check the sensor positions and conditions.
Temperature readings will be incorrect if the
sensors are touching the wall of an air hose or pipe or if the sensor or wiring is damaged.
The tip of the sensor should be centered within the air hose or pipe. Sensor wires should be
attached to the appropriate connection points on the dryer’s electrical enclosure or micro-
processor board.
5
To check with ohm meter,
measure the resistance across the
RTDs. The resistance . should be approximately 1100 ohm at
room temperature.
6
Replace the sensor, if necessary.
IMPORTANT
: Use only a
209758 Series part # RTD
from Conair. This dryer
uses a 1000 ohm RTD, NOT
a 100 ohm RTD. Verify you
have the correct part.
Summary of Contents for Carousel Plus D Series
Page 6: ...iv l Table of Contents...
Page 20: ...2 8 l Description...
Page 40: ...3 8 l Installation...
Page 54: ...4 14 l Operation Control Function Flow Charts From the Login Logout screen Home Login Screen 3...
Page 90: ...4 50 l Operation...
Page 112: ...5 16 l Maintenance...
Page 208: ...C 46 l Appendix...