This setpoint determines the delay which is used in evaluation of BusR V
unbal protection (threshold for this protection is set by the setpoint
).
12.2.8 Group: Pwr management
12.2.8.1
Setpoint: #Pwr mgmt mode
Group
Pwr management
Range [units]
ABS(kW), ABS(kVA), REL (%) [-]
Related FW
3.0
Description
ABS
(
K
W)
The power management is based on actual sum of active
power of gen-sets participating in the power management
in particular control group (
TotRunPact
) and sum of active
nominal power of gen-sets participating in the power
management in particular control group (
).
Setpoints #LoadResStrt X (e.g.
) and
#LoadResStop X (e.g.
) are set in absolute
values in kW.
ABS
(
K
VA)
The power management is based on actual sum of
apparent power of gen-sets participating in the power
management in particular control group (given by
TotRunPact
and total reactive power, S^2 = P^2 + Q^2)
and sum of apparent nominal power of gen-sets
participating in the power management in particular control
group (this value is given for each gen-set as
Nomin
current
multiplied by
GenNomV
). Setpoints #LoadResStrt
X (e.g.
) and #LoadResStop X (e.g.
) are set in absolute values in kVA.
REL
(%)
The power management is based on the relative load, i.e.
ratio active power to nominal power. Setpoints
#%LdResStrt X (e.g.
) and #%LdResStop X
(e.g.
) are set in relative values in %.
Minimum allowable relative power reserve is evaluated
from nominal power of all running gen-sets combined in %.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.