InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
302
15.2.1.41
Binary output: MODES: Aut mode
Related FW
3.0
Description
The output is closed while the controller is currently in AUT mode (either
switched by the mode selector on the front panel or by the input
15.2.1.42
Binary output: MODES: Off mode
Related FW
3.0
Description
The output is closed while the controller is currently in OFF mode (either
switched by the mode selector on the front panel or by the input
Remote
OFF
).
15.2.1.43
Binary output: MODES: Man mode
Related FW
3.0
Description
The output is closed while the controller is currently in MAN mode (either
switched by the mode selector on the front panel or by the input
).
15.2.1.44
Binary output: MODES: Aut mode
Related FW
3.0
Description
The output is closed while the controller is currently in AUT mode (either
switched by the mode selector on the front panel or by the input
15.2.1.45
Binary output: BusL Params OK
Related FW
3.0
Description
This output indicates that the BusL is healthy. The output is closed while
all
BusL electrical parameters
are in limits. If BTB is closed, the output
deactivates after the the delay for fixed voltage or frequency protections
elapses. If BTB is opened, the output deactivates immediately after electrical
parameters get out of limit (e.g. frequency, voltage, voltage unbalance etc.).
15.2.1.46
Binary output: BusR Params OK
Related FW
3.0