InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
305
15.2.1.54
Binary output: CtrlHeartBeat
Related FW
3.0
Description
The output provides alternating signal with rate 500ms active / 500ms
inactive while the controller is
operational
, i.e. it has passed all checks after
startup and no failure was detected.
If the output does not provide the alternating signal it may indicate following:
controller is switched off
or
controller is damaged
or
incorrect/missing firmware and/or application
or
corrupted setpoints
The output is intended for using in wired redundancy systems at the main
controller. Learn more about redundancy in separate chapter
Redundant
controllers
.
15.2.1.55
Binary output: BTB status
Related FW
3.0
Description
This output indicates the BTB position, how it is internally considered in the
controller. The position is based on
BTB feedback
input and optionally also
on the
If only the positive feedback input is used the output mirrors the
feedback.
If both feedbacks are used and they match each other the output
indicates the BTB position according to the feedbacks.
If both feedbacks are used, however they do not match each other,
the output remains in previous position when they matched.
The output can be used for indication of the BTB position.
15.2.1.56
Binary output: LdShed stage 1
Related FW
3.0
Description
This output is used for control of first load group. This is the group which is
disconnected as
first
one when the load shedding function becomes active.
Connect
least important
loads to this group.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.