InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
304
See the chapter
Timers
for more details about timers.
15.2.1.51
Binary output: TimerActiveCom
Related FW
3.0
Description
This is combined output from all timer channels. The output is active if at
least one timer channel is active.
15.2.1.52
Binary output: Synchro
Related FW
3.0
Description
The output is closed during reverse synchronizing and opens when the
output
is activated (= BTB was closed).
N
OTE
:
The output can be used for external synchronizing module control.
15.2.1.53
Binary output: In synchronism
Related FW
3.0
Description
This output is closed
during synchronization
when all synchro conditions
have been fulfilled. The output is opened either when:
the synchro conditions are lost
or
the corresponding breaker has been closed
or
the sychronizing was interrupted or timed out.
Synchro conditions are following:
Slip frequency is lower than 0.25 Hz
Phase shift between mains and bus (BusLeft and BusRight - in BTB
application) voltage must be within range of ±
period longer than
Voltage difference between mains and bus (BusLeft and BusRight -
in BTB application) voltage (in all phases) must be lower or equal to
for period longer than
The output is intended for manual synchronization. Automatic closing of BTB
must be disabled
for this case. Use the input