DATA-GSM:
This option sends a complete archive to the recipient's PC via GSM modem. A GSM
modem with activated CSD data transfers must be connected either to one of controller COM ports or
to one of I-LB modules connected to the controller via CAN2 bus. The channel address must contain
complete telephone number of the recipient's PC where InteliMonitor is running in Active call receiving
mode.
DATA-ISDN:
This option sends a complete archive to the recipient's PC via ISDN modem. An ISDN
modem must be connected either to one of controller COM ports or to one of I-LB modules connected
to the controller via CAN2 bus. The channel address must contain complete telephone number of the
recipient's PC where InteliMonitor is running in Active call receiving mode.
DATA-CDMA:
This option sends a complete archive to the recipient's PC via CDMA modem. A CDMA
modem must be connected either to one of controller COM ports or to one of I-LB modules connected
to the controller via CAN2 bus. The local CDMA network must allow point-to-point data transfers. The
channel address must contain complete telephone number of the recipient's PC where InteliMonitor is
running in Active call receiving mode.
SMS-GSM:
This option sends a short text message (SMS) containing the actual Alarmlist contents to
the recipient's mobile phone via the GSM modem. The channel address must contain complete
telephone number of the recipient's mobile phone.
SMS-CDMA:
This option sends a short text message (SMS) containing the actual Alarmlist contents
to the recipient's mobile phone via the CDMA modem. The channel address must contain complete
telephone number of the recipient's mobile phone.
IB-E-MAIL:
This option sends an e-mail containing the actual Alarmlist contents and latest 20 history
records (only date, time, reason) to the recipient's mailbox via the IB-COM module or IG-IB module.
The channel address must contain valid e-mail address of the recipient.
N
OTE
:
The SMTP settings (SMTP authent,SMTP user name, SMTP password, SMTP address, Contr
mailbox) must be properly adjusted for sending e-mails.
7.5.2
Example of setting
There is an example of setting of Remote Alarm Messaging. In this case active calls we be triggered
on
Breaker open
and
BrkOpen w/Reset
alarms.
Message
is
sent
via
to
[email protected] (Channel 1
– available for NTC controller or with any controller with
connected IB-NT or I-LB+), archive is sent via ISDN modem to the 111222333444 (Channel
2) and SMS is sent to the 999111333555 (Channel 3).
It is also possible to adjust number of attempts that controller performs in case of not successful Active
Call
–
Comms settings:
ActCallAttempt
. The language of messages can be changed
–
Comms settings:
Acall+SMS lang
(use Translator and Languages tabs in GenConfig to adjust
languages).