303
Description
This output indicates that the BusR is healthy. The output is closed while
all
BusR electrical parameters
are in limits. If BTB is closed, the output
deactivates after the the delay for fixed voltage or frequency protections
elapses. If BTB is opened, the output deactivates immediately after electrical
parameters get out of limit (e.g. frequency, voltage, voltage unbalance etc.).
15.2.1.47
Binary output: TimerAct 1-4
Related FW
3.0
Description
This is combined output from timer channels 1-4. The output is closed if at
least one of the channels is active.
N
OTE
:
See the chapter
Timers
for more details about timers.
15.2.1.48
Binary output: TimerAct 5-8
Related FW
3.0
Description
This is combined output from timer channels 5-8. The output is closed if at
least one of the channels is active.
N
OTE
:
See the chapter
Timers
for more details about timers.
15.2.1.49
Binary output: TimerAct 9-12
Related FW
3.0
Description
This is combined output from timer channels 9-12. The output is closed if at
least one of the channels is active.
N
OTE
:
See the chapter
Timers
for more details about timers.
15.2.1.50
Binary output: TimerAct 13-16
Related FW
3.0
Description
This is combined output from timer channels 13-16. The output is closed if at
least one of the channels is active.
N
OTE
: