InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
269
14.2.1.54
Binary input: ExtValue4 down
Related FW
3.0
Description
While this input is active the value of
ExtValue 4
is contiously beeing
N
OTE
:
If this input is used (configured), the
ExtValue 4
can't be written remotely
from a remote terminal using the command
ExtValue 4
.
14.2.1.55
Binary input: ExtValue1reset
Related FW
3.0
Description
The
ExtValue 1
is reset to it's default value when this input is activated and
held there until the input is deactivated. The default value is given by the
setpoint
While the reset input is active:
The value does not respond to up and down inputs.
The value does not accept new data that are written remotely from a
remote terminal using the
ExtValue
command.
N
OTE
:
Configuring of the reset input does not block writing the ExtValue remotely, in
comparison to the up and down inputs, which does. However, if the reset
input is active, the remotely written data are not accepted.
14.2.1.56
Binary input: ExtValue2reset
Related FW
3.0
Description
The
ExtValue 2
is reset to it's default value when this input is activated and
held there until the input is deactivated. The default value is given by the
setpoint
While the reset input is active:
The value does not respond to up and down inputs.
The value does not accept new data that are written remotely from a
remote terminal using the
ExtValue
command.
N
OTE
:
Configuring of the reset input does not block writing the ExtValue remotely, in