InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
160
. If none of these inputs is active the set #1 is selected.
N
OTE
:
The reserve for stop must be always adjusted higher than the reserve for
start.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.14
Setpoint: #%LdResStrt 1
Group
Pwr Management
Range [units]
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for start in relative mode. i.e.
= REL (%) if the reserve set #1 is active. Learn more about
reserves in the chapter
Reserves, minimal running power
.
The currently active reserve set is selected by binary inputs
. If none of these inputs is active the set #1 is selected.
N
OTE
:
If the relative power management is selected, this setpoint (or the setpoints
reserve set is selected) determines also the number of gensets (that are part
of the power management) which will start (according to their priority and
nominal power).
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.15
Setpoint: #%LdResStop 1
Group
Pwr Management
Range [units]
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for stop in relative mode. i.e.