InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
173
Related FW
3.0
Description
This setpoint adjusts the gain factor (P-factor) of the frequency control PI
loop. The integration factor (I-factor) for the frequency loop is adjusted by the
setpoint
A
PPLICATION
F
REQ GAIN AND
F
REQ INT SETPOINTS ARE ACTIVE DURING
:
BTB
synchronization between “left” and “right” buses
N
OTE
:
When this setpoint is set to zero, the corresponding control loop is switched
OFF.
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.
12.2.9.6
Setpoint: Freq int
Group
Sync ctrl
Range [units]
0 .. 100 [%]
Related FW
3.0
Description
This setpoint adjusts the relative integration factor (I-factor) of the frequency
control PI loop. The gain factor (P-factor) for the frequency loop is adjusted
by the setpoint
A
PPLICATION
F
REQ GAIN AND
F
REQ INT SETPOINTS ARE ACTIVE DURING
:
BTB
synchronization between “left” and “right” buses
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.