InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
110
Related FW
3.0
Description
The setpoint is used to adjust the busR voltage transformers ratio.
N
OTE
:
Adjust the setpoint to the value of
1.00
if the busR voltage is connected
directly to the controller terminals, i.e. without transformers.
N
OTE
:
Example: if you have transformers with ratio 6000/100V adjust the setpoint to
the value of
60.00
.
N
OTE
:
The range of the busR voltage inputs must be adjusted properly. See the
setpoint
12.2.2.4
Setpoint: VbRInpRangeSel
Group
Basic settings
Range [units]
277V, 120V [-]
Related FW
3.0
Description
This setpoint selects the range of the busR voltage terminals. The 120V
range is available only in IM-NTC hardware. The IM-NT has the range
adjusted fixedly to 277V regardless of this setpoint.
N
OTE
:
The 277V range is suitable for both European (230V) and American (277V)
measurement. The range 120V is intended for high-voltage applications
where voltage transformers with 100V secondary range are used or for
alternative American (120V) measurement.
12.2.2.5
Setpoint: BusLNomV
Group
Basic Settings
Range [units]
10 .. 30000 [V]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used to adjust the nominal mains voltage (phase to neutral).
If you do not know the phase-neutral nominal voltage, you can adjust the