Add or Remove Custom sensor curve
General type of sensor
Custom curve name
Resolution of
converted value
Add or Remove points from the curve
Order values from lowest to highest
Open curve points from file or save
current curve to file
Curve preview (no preview is
displayed if values or their order is
not valid)
Figure:
User Sensor definition
7.20 Languages and Translator tool in GenConfig
For detailed description of Languages and Translator tool please refer to GenConfig interactive help
(press F1 when in corresponding tab or open Help -> GenConfig Help).
7.21 Power Formats
InteliMains allows user to choose from several Power Formats that affect dimensions in which values
and some setpoints are interpreted or adjusted. Power formats may be changed in Miscellaneous tab
in GenConfig. There are following Power Formats available:
1 kW kVAr kVA kX V
0,1 kW kVAr kVA kX V
0,01 MW MVAr MVA MX kV
0,01 MW MVAr MVA MX V
N
OTE
:
Range of some setpoints and values is changed significantly when different Power Formats are
selected.
Last Power Format is designed to be used in combined High Power/High Voltage and Low Voltage
instalations. High voltage is then interpreted in Volts (e.g. 33256V instead of 33kV).
Last two Power Formats can be used in combination on one CAN bus.
7.22 User Mask function
In GenConfig you can easily set any object in Screen Editor to show or hide based on activation of
particular Logical Binary Input available for users. Below, there is diagram showing the setup of User
Mask function in Screen Editor.