InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
133
12.2.3.21
Setpoint: Gateway IP
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Description
this setpoint is used to adjust the IP address of
the gateway of the network segment where the controller is
connected.
this setpoint is used to display the
gateway IP address which has been assigned by the DHCP server. It
is not possible to change the setpoint value manually in this setting
(the value is immediately reverted back by controller communication
module IB-COM).
A gateway is a device which connects the respective segment with the other
segments and/or Internet.
12.2.3.22
Setpoint: ComApProtoPort
Group
Comms settings
Range [units]
1 .. 255 [-]
Related FW
3.0
Description
This setpoint is used to adjust the port, which is used for ethernet connection
to a PC with any of ComAp PC program (i.e. InteliMonitor, GenConfig).
This
setpoint should be adjusted to 23
, which is the default port used by all
ComAp PC programs. A different value should be used only in special
situations as e.g. sharing one public IP address among many controllers or to
overcome a firewall restrictions.
12.2.3.23
Setpoint: AirGate
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Description
This setpoint selects the ethernet connection mode.
DISABLED
This is a standard mode, in which the controller listens to
the incoming traffic and answers the TCP/IP queries
addressed to him. This mode requires the controller to be
accessible from the remote device (PC), i.e. it must be