15.2.1.26
Binary output: Common Hst
Related FW
3.0
Description
The output is closed for 1s when any alarm of
History record
type appears.
See the chapter
Alarm management
for more information.
15.2.1.27
Binary output: CommonActLev 1
Related FW
3.0
Description
The output is closed while there is at least one 1st level (yellow) alarm
present in the alarm list. The alarm can be in
any state
, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter
Alarm management
for more information.
15.2.1.28
Binary output: CommonAlLev 1
Related FW
3.0
Description
This output is active if there is at least one
unconfirmed
1st-level (yellow)
alarm present in the alarm list. See the chapter
Alarm management
for more
information.
15.2.1.29
Binary output: CommonActLev 2
Related FW
3.0
Description
The output is closed while there is at least one 2nd level (red) alarm present
in the alarm list. The alarm can be in
any state
, i.e. active unconfirmed,
active confirmed or inactive unconfirmed.See the chapter
Alarm management
for more information.
15.2.1.30
Binary output: CommonAlLev 2
Related FW
3.0
Description
This output is active if there is at least one
unconfirmed
2nd-level (red)
alarm present in the alarm list. See the chapter
Alarm management
for more
information.
15.2.1.31
Binary output: Alarm flashing
Related FW
3.0