InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
230
1. Go to GenConfig, download the configuration from the controller,
select the LAI tab and configure the logical analog input
MLC:AnExSysBld
, which is located in the
group. If you do not see the LAI tab you have to switch the
GenConfig to "advanced" mode. Then upload the configuration into
the controller.
2. Go to InteliMonitor and change the setpoint
MLoad ctrl PtM
to
ANEXSYSBLD->LS.
3. Now you have to program your PLC to write requested gen-set
baseload into the Modbus register
ExtValue1
(register number 40392
for IG/IS-NT-2.4).
13.1.6.2
Value: ExtValue2
Group
Force value
Units
-
Related FW
3.0
Description
This data object is intended for remote control of the IntelliMains via the
communication if some kind of data is to be passed into the controller.
This object can be written via the communication (e.g. Modbus) without any
limitation. Use GenConfig function Generate Cfg Image to get the
communication object number or register number of this particular value
object. See an example at the object
13.1.6.3
Value: ExtValue3
Group
Force value
Units
-
Related FW
3.0
Description
This data object is intended for remote control of the IntelliMains via the
communication if some kind of data is to be passed into the controller.
This object can be written via the communication (e.g. Modbus) without any
limitation. Use GenConfig function Generate Cfg Image to get the
communication object number or register number of this particular value
object. See an example at the object
13.1.6.4
Value: ExtValue4
Group
Force value