XAMPLE OF USING VIRTUAL PERIPHERIES FOR SIGNAL DISTRIBUTION
14.2.1.16
Binary input: Load res 3
Related FW
3.0
Description
This input is used to activate the
load reserve set #3
instead of the set #1,
which is active by default. The set #3 is adjusted by setpoints:
switched to absolute (kW-based) mode
and
switched to relative (%Pnom-based) mode.
C
AUTION
!
All controllers cooperating together in Power management must have
the
same load reserve set selected.