C0240111-04-05-GB
Para Description
Default
U.M.
Min.
Max.
052
Condenser pump enable (0:disabled - 1: enabled)
0
-
053
Secondary circuit pump control enable for water/water units (0:disabled - 1:
enabled)
0
-
054
Flow switch alarm bypass time when starting pump on secondary circuit
15
s
10
120
055
Flow switch alarm bypass time when stopping pump on secondary circuit
120
s
10
120
056
Maximum acceptable continuous operating time of a pump before rotation is
forced
7
d
1
1500
057
Maximum difference in days between the two pumps before the 'Threshold' value
of the pump is doubled
60
d
1
9999
058
Pump override enable during a long period of inactivity (0:No - 1:Yes)
1
-
059
Threshold time for long period of inactivity
30
d
1
1500
Duration of pump override for long period of inactivity
10
s
1
999
061
Continuous modulation enable of screw compressors (0:disabled - 1:enabled)
0
-
062
Minimum compressor shut-down time (with step adjustment)
60
s
1
500
063
Minimum delay between start-ups of different compressors (with input step
adjustment)
10
s
1 500
064
Minimum time between start-ups of the same compressor (with step adjustment)
360
s
1
500
065
Maximum number of compressor starts per hour (with Quick Mind adjustment)
8
-
1
12
066
Minimum compressor start-up time (with Quick Mind adjustment)
60
s
1
500
067
Pumpdown enable (0:disabled - 1:enabled)
0
-
068
Pumpdown time
3
s
1
60
069
Pumpdown setpoint
2.5
bar
0.1
7.0
Pumpdown differential (not used)
1.0
bar
0.1
3.0
071
Enables 100% screw compressor forcing (0:disabled - 1:enabled)
0
-
072
Minimum separation mode temperature setpoint
-5.0
°C
-30.0
0.0
073
Separation re-activation differential
1.0
°C
0.5 10.0
074
Period for power maintenance impulse
600
s
0
999
075
Period for power increase impulse
10
s
0
999
076
Minimum duration of power increase impulse
1.0
s
0.0
99.9
077
Maximum duration of power increase impulse
5.0
s
0.0
99.9
078
Period for power decrease impulse
10
s
1
999
079
Minimum duration of power decrease impulse
1.0
s
0.0
99.9
Maximum duration of power decrease impulse
5.0
s
0.0
99.9
081
No-load start time
30
s
1
60
082
Time the no-load valve remains open before the compressor starts
10
s
10
60
083
Minimum time the separation stages remain active
10
s
1
60
084
Time the compressor oil valve remains active
10
s
1
60
085
Compressor model (0:Bitzer - 1:Hitachi - 2:Fu-Sheng)
0
-
0
2
086
Economiser enable (0:disabled - 1:enabled)
0
-
087
Economiser start delay after compressor starts
120
s
1
500
088
Setpoint for disabling the economiser
15.0
bar
10.0
P253
089
Differential for disabling the economiser
2.0
bar
0.1
9.9
Enable compressor discharge temperature control, liquid injection (0:disabled -
1:enabled)
1
-
091
Setpoint for enabling discharge temperature control
115.0
°C
70.0
P228
092
Differential for disabling discharge temperature control
10.0
°C
2.0
25.0
093
Minimum percentage for modulating centrifuge compressors
30
%
0
50
094
Maximum percentage for modulating centrifuge compressors
93
%
50
100
095
Speed required to open the liquid line solenoid valve
1500
rpmx10
100
6000
096
Minimum start-up speed
1700
rpmx10
100
6000
097
Start-up time for centrifuge compressors
30
s
0
300
098
Integral time for power increase
2
s
1
120
099
Minimum variation for power increase
1
%
0
100
100
Integral time for power decrease
2
s
1
120
101
Minimum variation for power decrease
1
%
0
100
102
Off percentage for centrifuge compressor 1
0
%
0
P103
060
070
080
090
103
40
P102
On percentage for centrifuge compressor 1
%
100
69