C0240111-04-05-GB
> > 06.9
temperature expressed in degrees centigrade
>CDIN
The submask displays the inlet temperature of the condenser
> > 24.3
temperature expressed in degrees centigrade
>CDO1
The submask displays the outlet temperature of condenser 1
> > 22.3
temperature expressed in degrees centigrade
>CDO2
(If 2 condensers are present). The submask displays the outlet temperature of condenser 2
> > 22.4
temperature expressed in degrees centigrade
MAN
The manufacturer menu is not available on this keypad
>4H20
Only on the W3000 compact keypad
USER
User menu
>REG
The submask is used to set the adjustment type.
> > STEP
(Switch off the unit before changing this setting!!!). "STEP"= steps, "QM"= quick mind
326
>FLOU
The submask is used to set the adjustment flow type.
> > IN
"IN"= inlet flow, "OUT"= outlet type
327
>GO
(only visible in the Quick Mind adjustment mode). The submask is used to choose between two
types of start-up
> > STD
"STD"= standard, "FAST"= fast
328
>PROP
(Enable the "step adjustment" parameter first). The submask is used to set step adjustment.
> > P
"P"=proportional adjustment, "P+I"=propor integrative adjustment
330
>LL S
The submask is used to set the lower limit of the chiller setpoint with inlet adjustment
expressed in degrees centigrade
333
334
>HL S
The submask is used to set the upper limit of the chiller setpoint with inlet adjustment
> > 0
expressed in degrees centigrade
335
>LL S
The submask is used to set the lower limit of the chiller setpoint with outlet adjustment
expressed in degrees centigrade
336
>HL S
The submask is used to set the upper limit of the chiller setpoint with outlet adjustment
> > 0
expressed in degrees centigrade
337
>LL U
The submask is used to set the lower limit of the heat pump setpoint with inlet adjustment
> > 0
expressed in degrees centigrade
The submask is used to set the upper limit of the heat pump setpoint with inlet adjustment
> > 0
expressed in degrees centigrade
339
>LL U
The submask is used to set the lower limit of the heat pump setpoint with outlet adjustment
expressed in degrees centigrade
340
>HL U
The submask is used to set the upper limit of the heat pump setpoint with outlet adjustment
> > 0
expressed in degrees centigrade
341
>OFFS
(Only in the quick mind adjustment mode). The submask is used to set the forced shutdown
temperature in summer
> > 4.5
expressed in degrees centigrade
344
>OFFU
(Only in the quick mind adjustment mode). The submask is used to set the forced shutdown
temperature in winter
> > 42.5
expressed in degrees centigrade
345
(Only visible in the step adjustment mode). The submask is used to set the temperature
adjustment band
> > 0
expressed in degrees centigrade
346
>SETV
The submask is used to enable setpoint variation with an analogue signal
> > N
"N"= disabled, "Y"= enabled
349
>SETT
The submask is used to set the setpoint variation signal type.
"0-10"= 0-10 V, "4-20"= 4-20 mA
350
>SETL
The submask is used to set the minimum variation, corresponding to the minimum signal
> > 0
expressed in degrees centigrade
351
>SETH
The submask is used to set the maximum variation, corresponding to the maximum signal
> > 6.0
expressed in degrees centigrade
352
>P PR
(if 2 pumps are present on the evaporator). The submask is used to set the pump control type.
> > AUTO
"AUTO"= automatic, "PMP1"= pump 1 only, "PMP2"= pump 2 only
357
>P ON
The submask is used to set the minimum pump operation time when the unit is switched on
> > 0
> > 0
338
>HL U
> > 0
>BAND
> > 4 20
64