C0240111-04-05-GB
> > 60
time expressed in seconds
358
>P OF
The submask is used to set the minimum pump switch-off time when the unit is switched off
> > 60
time expressed in seconds
359
>PURL
The submask is used to enable power limiting
> > N
"N"=disabled, "Y"=enabled
360
>PURS
(If the "power limiting" parameter is enabled). The submask is used to set the power limitation
percentage in the summer mode
> > 50
value expressed in percent
361
>PURU
(If the "power limiting" parameter is enabled). The submask is used to set the power limitation
percentage in the winter mode
value expressed in percent
362
>DI O
The submask is used to set the digital input for switching on/off the unit
> > N
"N"= disabled, "Y"= enabled
364
>DI S
(Only if the "operating mode" parameter is set on the heat pump). The submask is used to
enable the digital input for summer/winter
> > N
"N"= disabled, "Y"= enabled
365
>BAND
The submask can be used to enable time bands
> > N
"N"= disabled, "Y"= enabled
366
>SER
The submask is used to enable the supervisor
> > N
"N"= disabled, "Y"= enabled
367
>PROT
(If the "supervisor" is enabled). The submask is used to set the communication protocol.
> > MODB
"MODB"= modbus, "LON"= lonWorks, "STD"=standard Carel
370
>BAUD
(If the "supervisor" is enabled). The submask is used to set the speed of communication
expressed in bauds
Possible values: "1200"-"2400"-"9600"-"19,2"=19200
371
>ID
(If the "supervisor" is enabled). The submask is used to set the identification n° for
communicating in the supervisor network
> > 0
ADDRESS
372
(If the "supervisor" is enabled). The submask is used to set on/off from the supervisor
> > N
"N"= disabled, "Y"= enabled
368
>SV M
(If the "supervisor" is enabled). The submask is used to enable the operating mode as
supervisor
> > N
"N"= disabled, "Y"= enabled
369
>PASS
The submask is used to set the user Password
> > 0
from 0 to 9999
CLH
Clock menu, not available on this keypad
>NONE
I/O
Input/output menu
>DI A
Displays digital input 1:4
> > CCCC
C=closed, A=open.
XXXX=[input1][input2][input3][input4]
>DI B
Displays digital input 5:8
> > CCCC
C=closed, A=open.
XXXX=[input5][input6][input7][input8]
Displays digital input 09:12:00
> > CCCC
C=closed, A=open.
XXXX=[input9][input10][input11][input12]
>DI D
Displays digital input 13:15
> > CCC
C=closed, A=open.
XXX-=[input13][input14][input15]
>DO A
Displays digital output 1:4
> > CAAA
C=closed, A=open.
XXXX=[output1][output2][output3][output4]
>DO B
Displays digital output 5:8
> > CAAA
C=closed, A=open.
XXXX=[output5][output6][output7][output8]
>DO C
Displays digital output 9:12
> > AAAA
C=closed, A=open.
XXXX=[output9][output10][output11][output12]
>AI 1
Displays analogue input 1
> > 18.1
value
> > 0
> > 1200
>SV O
>DI C
65