C0240111-04-05-GB
Para Description
Default
U.M.
Min.
322
Compressor 5 hour counter threshold
10
h x 1000
0
999
323
Compressor 6 hour counter threshold
10
h x 1000
0
999
324
Compressor 7 hour counter threshold
10
h x 1000
0 999
325
Compressor 8 hour counter threshold
10
h x 1000
0
999
326
Adjustment type (0:step - 1:Quick Mind)
1
-
327
Adjustment control type (0:inlet - 1:outlet)
1
-
Start-up mode (0:standard - 1:rapid)
0
-
329
Percentage inside the dead area in which the compressor is not modulated
(modulating screw compressors)
35
%
0
100
330
Step adjustment type (0: proportional - 1: propor integrative)
0
-
331
Inlet adjustment integral time
600
s
0
600
332
Integral correction limit
5
%
1
100
333
Minimum chiller setpoint (in the Quick Mind inlet adjustment mode)
11.0
°C
P909
P411
334
Minimum chiller setpoint (in the step inlet adjustment mode)
6.0
°C
P909
P412
335
Maximum chiller setpoint (with inlet adjustment)
20.0
°C
P910
23.0
336
Minimum chiller setpoint (with outlet adjustment)
6.0
°C
P909 P414
337
Maximum chiller setpoint (with outlet adjustment)
18.0
°C
P414
18.0
338
Minimum heat pump setpoint (with inlet adjustment)
30.0
°C
26.0
P413
339
Maximum heat pump setpoint (with inlet adjustment)
44.0
°C
P413
70.0
340
Minimum heat pump setpoint (with outlet adjustment)
30.0
°C
30.0
P415
341
Maximum heat pump setpoint (with outlet adjustment)
48.0
°C
P415
70.0
342
Minimum recovery setpoint
30.0
P343
°C
30.0
343
Maximum recovery setpoint
50.0
°C
P342
70.0
Forced summer shutdown
4.5
P232
P911
345
Forced winter shutdown
52.0
°C
P914
75.0
346
Temperature adjustment band (with step adjustment)
2.5
°C
2.0
10.0
347
Recovery adjustment band
5.0
°C
2.0
10.0
348
Enable secondary setpoint (0:No - 1:Yes)
0
-
349
Enable external setpoint variation (0:No - 1:Yes)
0
-
350
External setpoint variation type (0:4-20 mA - 1:0-10 V)
0
-
351
Minimum external setpoint
0.0
°C
0.0
10.0
352
Maximum external setpoint
6.0
°C
0.0
10.0
353
Enable external recovery setpoint variation (0:No - 1:Yes)
0
-
354
External recovery setpoint variation type (0:4-20 mA - 1:0-10 V)
0
-
Minimum external recovery setpoint
0.0
°C
0.0
356
Maximum external recovery setpoint
6.0
°C
0.0
10.0
357
Evaporator pump operating mode (0:automatic - 1:pump 1 only - 2:pump 2 only)
0
-
0
2
358
Minimum delay between pump start-up and compressor start-up
60
s
1
500
359
Pump shutdown delay
60
s
10
500
Enable power limitation (0:No - 1:Yes)
0
-
361
Power limitation in summer mode (%)
50
%
0
100
362
Power limitation in winter mode (%)
50
%
0
100
363
Power limitation in recovery mode (%)
50
%
0 100
364
On/off enable from digital input (0:No - 1:Yes)
0
-
365
Summer/winter enable from digital input (0:No - 1:Yes)
0
-
366
Time bands enable (0:deactivated - 1:activated)
0
-
367
Sequencer enable (0:deactivated - 1:activated)
0
-
368
Supervisor enable (0:Deactivated - 1:Activated)
0
-
369
Set communication protocol with supervisor (1:Standard - 2:ModBus -
3:LonWorks)
2
-
1
3
370
Speed of communication with supervisor setting (0:1200 baud - 1:2400 baud -
2:4800 baud - 3:9600 baud - 4:19200 baud)
3
-
0
4
371
Set unit identification number with supervisor
11
-
1
200
372
On/off enable from supervisor (0:No - 1:Yes)
0
-
373
Enable operating mode modification from supervisor (0:No - 1:Yes)
0
-
374
Language (1:Italian - 2:English - 3:Extra language)
1
-
1
3
Max.
328
344
°C
355
10.0
360
74