Access mask to user global parameters submenu. Press "Up" or "Down" to scroll
the other masks and "Esc" to return to the submenu.
Neutral area
centre : 050 %
Max. speed of temp.
variation : 6.0 °C/m
(Only visible in the quick mind adjustment mode). Used to centre the neutral
zone with respect to the setpoint. Also used to set the maximum water
temperature rise/fall speed. If this limit is exceeded a low water level message
will appear.
017
018
Override limit
at 100% 03.0 °C
Maximum range at
low loads 01.5 °C
Used to set the compressor override limit at 100% capacity. Used to set the
switching-on threshold of the first compressor with a very low load
019
020
Configuration of
compressor discharge
temperature probes:
NTC 0-150°C
Mask only visible in screw compressors that allow the type of discharge
temperature probe used to be selected.
021
Probe enable:
External temp. Y
Probe enable mask for enabling the external air temperature probe or condenser
inlet probe (Only visible where applicable)
022
023
Probe enable:
Pressure Y
Low pressure Y
Probe enable mask for enabling high and low pressure transducers.
024
025
Enter another
manufacturer
password
0000
Sets a new password.
ATTENTION: THE PASSWORD ENTERED IN THIS FIELD IS THE ONLY ONE
THAT ALLOWS ACCESS TO THE MANUFACTURER MENU!!
W 3000
Cod. CA 07.00 GB
nn
Man. C0240011-04-05
This mask contains the reference information of the software [Code CA07.00]
and of the reference user manual [Man.
C0240011-04-05
].
The closed padlock symbol shows that the card is provided with its propriety
software; two padlocks appear on units with 3 or 4 circuits
Functions
m
p
Access mask to functions submenu. Press "Up" or "Down" to scroll the other
masks and "Esc" to return to the submenu.
Setpoint
offset
Summer N
Winter N
Enables setpoint offset in summer and winter modes.
026
027
Summer offset
Set ext. air 45.0°C
Delta 05.0°C
Max var. set 06.0°C
Enables setting of external air temperature setpoint for activating summer
setpoint offset and defining the temperature delta at which the maximum
(positive) setpoint variation takes place.
028
029
030
Min. summer
setpoint offset
limit
07.0°C
Minimum summer setpoint limit with setpoint offset activated.
031
Winter offset
Set ext. air -05.0°C
Delta 05.0°C
Max var. set 05.0°C
Enables setting of external air temperature setpoint for activating winter setpoint
offset (but also in the recovery mode) and defining the temperature delta at
which the maximum (negative) setpoint variation takes place.
032
033
034
Max. winter
setpoint offset
limit
45.0°C
Maximum winter setpoint limit with setpoint offset activated.
035
HP relays
Enable Y
Enables the HP relays.
036
Upper set 10.0 bar
Upper diff. 05.0 bar
Lower set 09.5 bar
Lower diff. 00.5 bar
Sets the upper setpoint and differential and the lower setpoint and differential for
controlling the HP relays.
037
038
039
040
Subcooling
Enable N
Enables subcooling.
This function is only enabled in units with recovery mode.
041
Subcooling
Adjustment start
delay 060 s
Relay delay 030 s
Sets the delay before subcooling adjustment commences and the delay in the
subcooling relay.
042
043
Subcooling
Upper s. 04.0 °C
Lower set 03.0 °C
Sets the upper and lower sub cooling setpoint.
044