C0240111-04-05-GB
Para Description
Default
U.M.
Min.
Max.
212
Forced defrosting pressure threshold
1.0
bar
P221
9.9
213
Minimum heatpump operating pressure for separating hermetic compressors
1.2
bar
P221
9.9
214
Restore pressure for separating the hermetic compressors
1.6
bar
P213
9.9
215
Free defrost enable (0:disabled - 1:enabled)
0
-
216
Minimum external temperature for free defrost operation
4.0
°C
-10.0
10.0
217
High pressure from transducers alarm
28.0
bar
0.0
P253
218
High pressure from transducers alarm differential
7.0
bar
0.0
30.0
219
N° low pressure alarm repetitions
3
-
0
5
220
Duration of low pressure alarm
120
s
0
500
221
Low pressure alarm setpoint
1.6
bar
0.1
9.9
222
Low pressure alarm differential
0.9
bar
0.1
4.0
223
Enable low pressure control with low external air temperature (0:No - 1:Yes)
0
-
224
Start-up time for low pressure control with low external air temperature
120
s
10
P220
225
Low pressure setpoint with low external air temperature
0.1
bar
0.1
P221
226
Low pressure differential with low external air temperature
0.5
bar
0.1
4.0
227
Bypass time of compressor thermal protection alarm
10
s
0
360
228
Setpoint for activating the high compressor discharge temperature alarm
125.0
°C
70.0
125.0
229
Differential for deactivating the high compressor discharge temperature alarm
10.0
°C
2.0
25.0
230
Compressor oil alarm delay after starting
120
s
1
120
231
Compressor oil alarm delay during running
10
s
1
120
232
Evaporator antifreeze alarm setpoint
4.0
°C
-30.0
5.0
233
Evaporator antifreeze alarm differential
4.0
°C
1.0
10.0
234
Evaporator antifreeze heating element setpoint
4.0
°C
P232
5.0
235
Evaporator antifreeze heating element differential
4.0
°C
1.0
10.0
236
Condenser antifreeze alarm setpoint
4.0
°C
-30.0
5.0
237
Condenser antifreeze alarm differential
4.0
°C
1.0
10.0
238
Recuperator antifreeze heating element setpoint
4.0
°C
-30.0
5.0
239
Recuperator antifreeze heating element differential
4.0
°C
1.0
10.0
240
Evaporator flow meter start-up delay
10
s
1 120
241
Evaporator flow switch running delay
1
s
1
20
242
Recuperator flow switch start-up delay
10
s
1
120
243
Recuperator flow meter running delay
1
s
1
20
244
Condenser flow meter start-up delay
10
s
1
120
245
Condenser flow meter running delay
1
s
1
20
246
High/low inlet temperature (0:signal - 1:alarm)
0
-
247
High/low inlet temperature alarm delay
30
s
1 999
248
High inlet water temperature alarm setpoint
30.0
°C
P912
30.0
Low inlet water temperature alarm setpoint
15.0
°C
15.0
250
Low water flow alarm setpoint
8.0
°C
3.0
10.0
251
Low water flow alarm delay
30
s
P240
30
252
Start scale value of high pressure transducers
0.0
bar
0.0
P253
253
End scale value of high pressure transducers
30.0
bar
P252 42.0
254
Start scale value of low pressure transducers
0.0
bar
0.0
P255
255
End scale value of low pressure transducers
30.0
bar
P254
30.0
256
Probe 1 calibration
°C/bar
0.0
-9.9
9.9
257
Probe 2 calibration
0.0
°C/bar
-9.9
9.9
258
Probe 3 calibration
0.0
°C/bar
-9.9
9.9
259
Probe 4 calibration
0.0
°C/bar
-9.9
9.9
260
Probe 5 calibration
0.0
°C/bar
-9.9
9.9
261
Probe 6 calibration
0.0
°C/bar
-9.9
9.9
262
Probe 7 calibration
0.0
°C/bar
-9.9 9.9
263
Probe 8 calibration
0.0
°C/bar
-9.9
9.9
264
Probe 9 calibration
0.0
°C/bar
-9.9
9.9
265
Probe 10 calibration
0.0
°C/bar
-9.9
9.9
266
Probe 1 expansion 1 calibration
0.0
°C/bar
-9.9
9.9
249
P913
72