C0240111-04-05-GB
Hour counter
Compressor 4:
Threshold 010x1000
Reset N° 000000
Sets the threshold for programmed maintenance.
321
Hour counter
Compressor 5:
Threshold 010x1000
Reset N° 000000
Sets the threshold for programmed maintenance.
322
Hour counter
Compressor 6:
Threshold 010x1000
Reset N° 000000
Sets the threshold for programmed maintenance.
323
Hour counter
Compressor 7:
Threshold 010x1000
Reset N° 000000
Sets the threshold for programmed maintenance.
324
Hour counter
Compressor 8:
Threshold 010x1000
Reset N° 000000
Sets the threshold for programmed maintenance.
325
Default
m
p
Access mask to initialisation menu. Press "Up" or "Down" to scroll the other
mask and "Esc" to return to the submenu.
The mask is not displayed when the chiller is ON.
Reset chiller to
default values
N
This restores the default values.
The chiller must then be programmed with the parameter set during factory
testing.
User
m
p
Access mask to user menu. Press "Up" or "Down" to scroll the other masks and
"Esc" to return to the submenu.
Step adjustment
type
IN INLET
Chooses between step adjustment and Quick Mind adjustment. Also defines on
which temperature probe the adjustment is made. If the unit has more than one
evaporator or step adjustment is set, adjustment can only be made on the inlet
probe.
326
327
Start-up mode
standard
Chooses between standard or rapid start-up (only displayed in the Quick Mind
adjustment mode)
328
Amplitude of stable
zone:
023 %
Sets the percentage inside the dead area around the setpoint in which the
compressor is not modulated. (only for modulating screw compressors)
329
Input adjustment:
Type PROPORTIONAL
Defines the type of adjustment. (only visible in the step inlet adjustment mode)
330
Integral time:
0600 s
Integral correction
limit: 005 %
Sets integration time and correction limit (displayed in the step inlet adjustment
mode with propor integral adjustment type)
331
332
Setpoint limits
chiller:
Low 11.0 °C
High 20.0 °C
Maximum and minimum setpoint values that can be set with inlet adjustment
N.B.: For low temperature units, the minimum value that can be set for the low
limit is equal to the antifreeze se2°C (also check the value set for forced
shut-down in the Quick Mind adjustment mode).
333
334
335
Setpoint limits
chiller:
Low 06.0 °C
High 18.0 °C
Maximum and minimum setpoint values that can be set with outlet adjustment
N.B.: For low temperature units, the minimum value that can be set for the low
limit is equal to the antifreeze se2°C (also check the value set for forced
shut-down in the Quick Mind adjustment mode).
336
337
Setpoint limits
heat pump:
Low 30.0 °C
High 44.0 °C
Maximum and minimum setpoint values that can be set with inlet adjustment
(only visible if the heat pump configuration is set)
338
339
Setpoint limits
heat pump:
Low 30.0 °C
High 48.0 °C
Maximum and minimum setpoint values that can be set with outlet adjustment
(only visible if the heat pump configuration is set)
340
341
Setpoint limits
recovery:
Low 30.0 °C
High 50.0 °C
Maximum and minimum recovery setpoints. (only visible if recovery is
configured)
342
343
Forced shutdown
Summer 04.5 °C
Winter 52.0 °C
(Only in the Quick Mind adjustment mode) Forces the compressors to shut down
if:
Tout summer < summer minimum
or
Tout winter > winter maximum
344
345
53