C0240111-04-05-GB
Power decr. impulse:
Period: 001 s
Min. dur.: 01.5 s
Max. dur.: 03.0 s
Sets the period and duration of the power decrease impulse.
078
079
080
Compressor start
time: 30 s
No-load valve
pre-open time: 10 s
Sets the start-up time of the compressor, that, is, the time the compressor
remains in the no-load start mode before it starts adjusting.
Sets the time the no-load start valve remains open before the compressor starts.
081
082
Min. time sep.
stages active:
10 s
Sets the minimum time the separation stages remain active.
083
Time compressor oil
valve active 10 s
Sets the time the compressor oil valve remains active.
084
Model:
Bitzer
Sets the compressor model.
085
Economiser:
Enable Y
Start delay 120 s
Enables the economiser and sets the start delay.
086
087
Economiser
disable:
Setpoint 15.0 bar
Diff. 2.0 bar
Sets the setpoint and differential for disabling the economiser.
088
089
Compressor discharge
temperature control
Enabled: Y
Enables compressor discharge temperature control for liquid injection.
090
Compressor discharge
temperature control
Setpoint 115.0 °C
Diff. 10.0 °C
Sets the setpoint and differential for liquid injection.
091
092
Compressor
modulation
Minimum: 040 %
Maximum: 091 %
Sets minimum and maximum values for compressor modulation.
093
094
Start revs: 15000
Minimum revs: 17000
Compressor start
time: 030 sec
Sets the minimum number of revs for opening the liquid line solenoid valve
starting the compressor.
Also sets the minimum number of revs for starting the compressors and the time
the minimum revs are maintained during start-up.
095
096
097
Power request
increase
Integral T. 002 sec
Minimum Var. 001 %
Sets the integral time and minimum variation for increasing the power request.
098
099
Power request
decrease
Integral T. 002 sec
Minimum Var. 001 %
Sets the integral time and minimum variation for decreasing the power request.
100
101
Centrifuge Comp.
off: on:
Comp. 1 000% 040%
Comp. 2 000% 040%
Sets the enable and disable percentage for each centrifuge compressor.
102
103
104
105
Centrifuge Comp.
off: on:
Comp. 3 000% 040%
Comp. 4 000% 040%
Sets the enable and disable percentage for each centrifuge compressor.
106
107
108
109
Centrifuge Comp.
off: on:
Comp. 5 000% 040%
Comp. 6 000% 040%
Sets the enable and disable percentage for each centrifuge compressor.
110
111
112
113
Centrifuge Comp.
off: on:
Comp. 7 000% 040%
Comp. 8 000% 040%
Sets the enable and disable percentage for each centrifuge compressor.
114
115
116
117
46