C0240111-04-05-GB
Unit
m
p
Access mask to unit menu. Press "Up" or "Down" to scroll the other masks and
"Esc" to return to the submenu.
Temp. In. Out.
Evap. 12.5 07.0°C
Rec. 35.6 40.5°C
Cond. 38.0 42.5°C
Displays inlet and outlet temperatures of the evaporator, recuperator and
condenser (where fitted).
Temp. In. Out.
Evap. 12.5 07.0°C
Evap1 07.2°C
Evap2 06.9°C
(if 2 evaporators are fitted) Displays inlet and outlet temperatures of the
evaporator or condenser (depending on whether the unit is in the summer or
winter mode) and the outlet temperature of the two evaporators.
Temp. In. Out.
Cond. 24.3 22.4°C
Cond.1 22.3°C
Cond.2 22.4°C
(if 2 condensers are fitted) Displays inlet and outlet temperatures of the
evaporator or condenser (depending on whether the unit is in the summer or
winter mode) and the outlet temperature of the two condensers.
Temp.
External air 05.3°C
Freecooling 06.0°C
Displays temperature or external air or freecooling. (if probes are fitted)
Circ1 Circ2
hp 07.3 07.3bar
lp 04.2 03.9bar
st Off Off
Displays high and low pressure values (if transducers are fitted) and codifies the
operating mode of circuits 1 and 2.
Circ3 Circ4
hp 07.3 07.3bar
lp 04.2 03.9bar
st Off Off
Displays high and low pressure values (if transducers are fitted) and codifies the
operating mode of circuits 3 and 4.
Circ1 Circ2
tc 07.3 07.3 °C
tl 00.0 00.0 °C
sub 00.0 00.0 °C
(in chiller units with recovery) Displays pressure converted into temperature
values, temperature of the liquid and calculated subcooling values of circuits 1
and 2.
Circ3 Circ4
tc 07.3 07.3 °C
tl 00.0 00.0 °C
sub 00.0 00.0 °C
(in chiller units with recovery) Displays pressure converted into temperature
values, temperature of the liquid and calculated subcooling values of circuits 3
and 4.
Timer tuning defrost
Range 1200 - 03600 s
Free Defrost 0370 s
Displays, for timer tuning defrost, the variation range in the defrost delay
according to external temperature.
Also displays the maximum duration of the free defrost procedure according to
external temperature.
Circ1 Circ2
Time 02700 02700 s
Timer tuning defrost
Displays the defrost delay calculated by the timer tuning defrost algorithm.
Circ3 Circ4
Time 02700 02700 s
Timer tuning defrost
Displays the defrost delay calculated by the timer tuning defrost algorithm.
Circ1 Circ2
Time 0188 0125 s
Max 0290 0270 s
Free Defrost
Displays the free defrost enable time and the maximum procedure time
according to the length of the delay.
Circ3 Circ4
Time 0188 0125 s
Max 0290 0270 s
Free Defrost
Displays the free defrost enable time and the maximum procedure time
according to the length of the delay.
Circ1 Circ2
defr N N
Delay 0904 0000 s
T.def 0000 0028 s
Displays the defrosting status of circuits 1 and 2, the delay before defrosting
starts and the time taken to defrost.
Circ3 Circ4
defr N N
Delay 0904 0000 s
T.def 0000 0028 s
Displays the defrosting status of circuits 3 and 4, the delay before defrosting
starts and the time taken to defrost.
Discharge time
Comp.1 105.3°C
Comp.2 098.4°C
Displays the discharge temperature (if probes are present) of compressors 1 and
2.
Discharge time
Comp.3 105.3°C
Comp.4 098.4°C
Displays the discharge temperature (if probes are present) of compressors 3 and
4.
Analogue outputs:
Cond. 1 adj.:000 %
Cond. 2 adj.:000 %
Displays analogue outputs 1 and 2. Shows the percentage of demand of the
devices connected to it (for non-linear devices correspondence with supplied
voltage V does not apply). Compares Cond.1-2 adj. with single or dual ventilation
adjustment.
60