C0240111-04-05-GB
Compressor revs
reading conversion
0-390mV - 0-48000rpm
Sets the voltage and revs for converting the signal from the compressors.
118
119
Valves
m
p
Access mask to valves submenu. Press "Up" or "Down" to scroll the other masks
and "Esc" to return to the submenu.
Status configuration
S0 => off
Valves:
CCCCCCCCCC => 0000
Status editor mask.
Configures the valves (A=valve open, C=valve closed) in each status (S0,S1,…
S12).
Valve configuration is automatically converted.
120
121
122
123
124
125
126
127
128
129
130
131
132
Valve release
time: V1: 000 s
V2: 000 s V3: 000 s
V4: 000 s V5: 000 s
Sets the valve release time.
133
134
135
136
137
Valve release
time: V6: 000 s
V7: 000 s V8: 000 s
V9: 000 s V10:000 s
Sets the valve release time.
138
139
140
141
142
C1: off
valve:CCCCCCCCCC
C2: off
valve:CCCCCCCCCC
Visualises the status of the circuits and the valves of the circuit.
C3: off
valve:CCCCCCCCCC
C4: off
valve:CCCCCCCCCC
Visualises the status of the circuits and the valves of the circuit.
Recovery
m
p
Access mask to recovery submenu. Press "Up" or "Down" to scroll the other
masks and "Esc" to return to the submenu.
Winter
priority: N
Sets recovery priority in winter.
143
Enable
remote recovery
control: N
Enables recovery control from a remote contact.
144
Chiller override fm
recovery pressure
Setpoint 23.5 bar
Diff. 5.0 bar
Defines the pressure setpoint and differential at which the recovery mode is
forced to chiller.
145
146
Minimum time in
chiller status
from recovery
120 s
Time in chiller status after switching from recovery.
147
Condens.
m
p
Access mask to condensation submenu. Press "Up" or "Down" to scroll the other
masks and "Esc" to return to the submenu.
Condensation control
Enable : Y
Type : Step Cont.
N° steps : 4
Enables condensation control, the type and number of steps.
148
149
150
47