5.3) SETPOINT MENU
Different setpoints can be set depending on the available operating modes (chiller, heat pump and
recovery).
Secondary setpoint values can also be set for chiller and heat pump operation (only if the digital input is
fitted and the “secondary setpoint” function is enabled in the “user menu”).
5.4) CLOCK MENU
The clock menu is not enabled in the W3000 base.
After enabling time bands from the “enable time bands” parameter in the “user menu”, time bands can
be set and specific operating modes and different setpoints can be set according to requirements.
Several time bands (up to 5) can be set within a 24 hour period.
Figure 5.10 shows an example: the beginning of the first time band is set at 00:00 and the end of the
fifth time band is set at 23:59; the end of one time band determines the beginning of the following one.
To use a smaller number of bands, set the time a band ends to the same time it begins, and that band
will be ignored. Summer and winter setpoints and unit On/Off switching can be set for each time band. If
the unit is switched Off, it will remain in the “Off from time bands” mode.
Adjustment
Unit off
Figure 5.10:
example of setting time bands