1-23
Cisco ONS 15454 Procedure Guide, R5.0
March 2005
Chapter 1 Install the Shelf and Backplane Cable
NTP-A11 Install the Rear Cover
Note
As needed, attach additional standoffs to the extended standoffs to meet site-specific cable
management requirements.
Step 3
Locate the mounting holes where you will install the standoffs on the EIAs you are using.
shows the mounting holes on the UBIC-V.
shows the mounting holes on the UBIC-H.
shows the mounting holes on the remaining EIA types (MiniBNC, SMB, etc.). You can
identify the mounting holes on all EIAs by locating the
REAR COVER BRACKET LOCATION
designation.
Table 1-4
Standoffs Required for EIA Types
EIA Type
Required Standoffs for
One Extended Standoff
Total Required
Standoffs per Shelf
UBIC-V
One 1 3/8-inch
Two 2-inch
Four 1 3/8-inch
Eight 2-inch
UBIC-H
One 1 3/8-inch
One 2-inch
Four 1 3/8-inch
Four 2-inch
MiniBNC
One 1 3/8-inch
One 2-inch
Four 1 3/8-inch
Four 2-inch
BNC
One 1 3/8-inch
One 1-inch
Four 1 3/8-inch
Four 1-inch
High-Density BNC
SMB
AMP Champ