4-6
Cisco ONS 15454 Procedure Guide, R5.0
December 2004
Chapter 4 Turn Up Node
NTP-A261 Set Power Monitor Thresholds
•
Time Zone—Click the field and choose a city within your time zone from the drop-down list. The
menu displays the 80 World Time Zones from –11 through 0 (GMT) to +14. Continental United
States time zones are GMT-05:00 (Eastern), GMT-06:00 (Central), GMT-07:00 (Mountain), and
GMT-08:00 (Pacific).
•
Use Daylight Savings Time—Check this check box if the time zone that you chose is using Daylight
Savings Time.
•
Insert AIS-V on STS-1 SD-P—Check this check box if you want Alarm Indication Signal Virtual
Tributary (AIS-V) conditions inserted on VT circuits carried by STS-1s when the STS-1 crosses its
Signal Degrade Path (SD-P) bit error rate (BER) threshold. On protected circuits, traffic will be
switched. If the switch cannot be performed, or if circuits are not protected, traffic will be dropped
when the STS-1 SD-P BER threshold is reached.
•
SD-P BER—If you selected Insert AIS-V, you can choose the SD-P BER level from the SD-P BER
drop-down list.
Step 4
Click
Apply
.
Step 5
In the confirmation dialog box, click
Yes
.
Step 6
Review the node information. If you need to make corrections, repeat Steps
through
to enter the
corrections. If the information is correct, continue with the
“NTP-A261 Set Power Monitor Thresholds”
.
Stop
.
You have completed this procedure
.
NTP-A261 Set Power Monitor Thresholds
Step 1
Complete the
“DLP-A60 Log into CTC” task on page 17-66
for the node you will set up. If you are
already logged in, continue with Step 2.
Step 2
In node view, click the
Provisioning > General > Power Monitor
tabs.
Step 3
To change the extreme low battery voltage threshold in 0.5 VDC increments, choose a voltage from the
ELWBATVGVdc drop-down list.
Step 4
To change the low battery voltage threshold in 0.5 VDC increments, choose a voltage from the
LWBATVGVdc drop-down list.
Step 5
To change the high battery voltage threshold in 0.5 VDC increments, choose a voltage from the
HIBATVGVdc drop-down list.
Purpose
This procedure provisions extreme high, high, extreme low, and low input
battery power thresholds within a –48 volts direct current (VDC)
environment. When the thresholds are crossed, the TCC2/TCC2P
generates warning alarms in CTC.
Tools/Equipment
None
Prerequisite Procedures
NTP-A24 Verify Card Installation, page 4-2
Required/As Needed
Required
Onsite/Remote
Onsite or remote
Security Level
Provisioning or higher
Summary of Contents for ONS 15454 Series
Page 28: ...Tables xxviii Cisco ONS 15454 Procedure Guide R5 0 December 2004 ...
Page 44: ...Tasks xliv Cisco ONS 15454 Procedure Guide R5 0 December 2004 ...
Page 53: ...liii Cisco ONS 15454 Procedure Guide R5 0 December 2004 About this Guide Document Conventions ...
Page 55: ...lv Cisco ONS 15454 Procedure Guide R5 0 December 2004 About this Guide Document Conventions ...
Page 850: ...Index IN 22 Cisco ONS 15454 Procedure Guide R5 0 December 2004 description 4 11 remove 18 23 ...