17-44
Cisco ONS 15454 Procedure Guide, R5.0
March 2005
Chapter 17 DLPs A1 to A99
DLP-A36 Install the TCC2/TCC2P Cards
•
All LEDs (including the CRIT, MAJ, MIN, REM, SYNC, and ACO LEDs) blink once and turn
off for about 10 seconds.
•
Both green PWR LEDs turn on for 5 seconds. The PWR LEDs then turn red for 2 to 3 minutes
before going to steady green.
•
The yellow ACT/STBY turns on and the PWR LEDs turn red for 2 to 3 minutes. (The Sync LED
might be green at this time.)
•
The yellow ACT/STBY LED turns on. (The ACT/STBY LED might take several minutes to turn
on while the DCC processor boots.)
Note
It might take up to 3 minutes for the A and B power alarms to clear.
Note
Alarm LEDs might be on; disregard alarm LEDs until you are logged into CTC and can view the
Alarms tab.
Note
If you are logged into CTC, the SFTWDOWN alarm might appear as many as two times while
the TCC2P card initializes. The alarm should clear after the card completely boots.
Note
If the FAIL LED is on continuously, see the tip below about the TCC2P card automatic upload.
Step 5
Verify that the ACT/STBY LED is green if this is the powered-up TCC2/TCC2P card installed, or yellow
for standby if this is the second powered-up TCC2/TCC2P. The IP address, temperature of the node, and
time of day appear on the LCD. The default time and date is 12:00 AM, January 1, 1970.
Step 6
The LCD cycles through the IP address, node name, and software version. Verify that the correct
software version displays on the LCD.
Step 7
If the LCD shows the correct software version, continue with
. If the LCD does not show the
correct software version, upgrade the software or remove the TCC2/TCC2P card and install a
replacement card.
Refer to the release-specific software upgrade document to replace the software. To exchange the
TCC2/TCC2P card, see the
Cisco ONS 15454 Troubleshooting Guide
.
Step 8
Repeat Steps
through
for the redundant TCC2/TCC2P card.
Tip
If you install a standby TCC2/TCC2P card that has a different software version than the active
TCC2/TCC2P card, the newly installed standby TCC2/TCC2P card automatically copies the
software version from the active TCC2/TCC2P card. You do not need to do anything in this
situation. However, the loading TCC2/TCC2P card does not boot up in the normal manner. When
the standby card is first inserted, the LEDs follow most of the sequence listed in
. After
the red FAIL LED turns on for about 5 seconds, the FAIL LED and the ACT/STBY LED begin
to flash alternately for up to 30 minutes while the new software loads onto the active
TCC2/TCC2P card. After loading the new software, the upgraded TCC2/TCC2P card’s LEDs
repeat the sequence from
, and the amber ACT/STBY LED turns on.
Summary of Contents for ONS 15454 Series
Page 28: ...Tables xxviii Cisco ONS 15454 Procedure Guide R5 0 December 2004 ...
Page 44: ...Tasks xliv Cisco ONS 15454 Procedure Guide R5 0 December 2004 ...
Page 53: ...liii Cisco ONS 15454 Procedure Guide R5 0 December 2004 About this Guide Document Conventions ...
Page 55: ...lv Cisco ONS 15454 Procedure Guide R5 0 December 2004 About this Guide Document Conventions ...
Page 850: ...Index IN 22 Cisco ONS 15454 Procedure Guide R5 0 December 2004 description 4 11 remove 18 23 ...