1 Operational Manual
the stroke checking time (Tim 53) of high-pressure cylinder in menu 39.
(B) Remedy:
a) Check the opening end and closing end signal (Input 19, Input 12).
b) Check the high-pressure directional control valve.
c) Modify stroke check time Tim 53 on Menu 39A.
TIMER REVIEW MONITORING PAGE 1
DESCRIPTION SET TURE DESCRIPTION SET TURE
INJECTION TIME AAAA.A ????.? COOLING TIME BBBB.B ????.?
INTERMISSION CCCC.C ????.? CYCLE TIME DDDD.D ????.?
EJECT PAUSE EEEE.E ????.? SPARE 05 FFFF.F ????.?
LOW PR.-ALARM GGG.GG ???.?? FEEDING DELAY HHH.HH ???.??
FEED OPEN ALARM IIII.I ????.? NOZ. FORWARD FAST JJJ.JJ ???.??
NOZ. FOR. STROKE KKK.KK ???.?? NOZZLE BACKWARD LLL.LL ???.??
CORE 1 IN MMMM.M ????.? CORE 1 OUT NNNN.N ????.?
CORE 2 IN OOOO.O ????.? CORE 2 OUT PPPP.P ????.?
FAST UNSCREW-IN QQQQ.Q ????.? SLOW UNSCREW-IN RRRR.R ????.?
FAST UNSCREW-OUT SSSS.S ????.? SLOW UNSCREW-OUT TTTT.T ????.?
3STEP UNSCR BACK UUUU.U ????.? HOLDING PR.1 VVVV.V ????.?
HOLDING PR.2 WWWW.W ????.? HOLDING PR.3 XXXX.X ????.?
EJECTION DELAY YYYY.Y ????.? AIRBLOW T. OPENING ZZZZ.Z ????.?
AIRBLOW DELAY OPEN aaa.aa ???.?? AIRBLOW TIME OPEN bbb.bb ???.??
LUBRICATION TIME ccc.cc ???.?? LUBRICATION ALARM ddd.dd ???.??
ACCUMLATOR ALARM eee.ee ???.?? ACCUM. PRESSURIZED fff.ff ???.??
Menu39A
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
3.24 “039 Check Limit Switch of Mold Screw”
(A) Conditions:
a) Mold Screw L.S. did not finish its task at given time, warning message will appear.
b) Mold Screw out L.S. signal
“
input 37
”
and in signal
“
input 36
”
are on
simultaneously.
c) Mold Screw out L.S.
“
input 37
”
is not on (OFF) while intending to do ejector
forward.
(B) Remedy:
a) Check the circuit of Input 37 and Input 36.
b) Modify the stroke check time (Mold screw in JJJJ.J, Mold screw out QQQQ.Q)and
04/08/13
169