Chapter 6 - Parameter Description
6-10
DRV T/K 0.0A
00 STP 30.00 Hz
DRV Cmd. Freq
00 30.00 Hz
DRV Step freq-1
01 10.00 Hz
DRV Step freq-1
15 30.00 Hz
DRV Current
17 7.6A
DRV Speed
18 1350RPM
DRV DC Link Vtg
19 646.0V
DRV User Disp
20 Out 424.0V
6.2 Drive Group [DRV]
)**+ 1
!
" 2' !
' '
" 2' !
! 1'"" !
DRV-00 Main Scree
DRV-00 Parameter
When [Enter] key is pressed in DRV-00 screen the
display will enter programming mode for the
Command Frequency and a flashing cursor will be
displayed which can be moved with the [Shift] key.
When [Enter] key is pressed after the Command
Frequency number (Hz) has been changed, the
display will show DRV-00 screen with new speed
command. The DRV-00 screen will show actual
VFD output frequency instead of Command
Frequency when VFD starts running the motor.
If PID control is enabled, DRV-00 screen will
display PID set point while in stop mode and actual
output frequency while in run mode.
When DRV-24 is changed from Hz to RPM, the
DRV-00 screen will show Speed reference and
actual Speed in RPM.
)* A
) 7+
" 2' !
A 7
The Step Frequencies are the preset speeds
activated by a binary coded combination of four
programmable digital inputs set to Speed-L, M, H,
and X in parameters I/O-20 ~I/O-27. The table
below shows all digital input combinations for the
15 possible preset speeds.
SPEED
Parameter
Step
Speed
X
(8)
H
(4)
M
(2)
L
(1)
0
0
0
0
-
N/A
0
0
0
1
DRV-01
Speed 1
0
0
1
0
DRV-02
Speed 2
0
0
1
1
DRV-03
Speed 3
0
1
0
0
DRV-04
Speed 4
0
1
0
1
DRV-05
Speed 5
0
1
1
0
DRV-06
Speed 6
0
1
1
1
DRV-07
Speed 7
1
0
0
0
DRV-08
Speed 8
1
0
0
1
DRV-09
Speed 9
1
0
1
0
DRV-10
Speed 10
1
0
1
1
DRV-11
Speed 11
1
1
0
0
DRV-12
Speed 12
1
1
0
1
DRV-13
Speed 13
1
1
1
0
DRV-14
Speed 14
1
1
1
1
DRV-15
Speed 15
) 0+ B - " 2' !
If any digital input I/O-
20~27 is programmed
to
Jog_FX
or
Jog_RX
and activated, the VFD will
run forward or reverse at DRV-16 Jog Speed based
on ACC or DEC time until input is disabled.
) 36 46 5+
> " ' ' 1'"" ! 6
"
!
1 ;'
-
DRV-17 shows the actual motor current.
DRV-18 shows the actual motor speed.
DRV-19 shows the actual DC bus voltage
DRV-20 shows the actual VFD output voltage or
kW selected in FG2-81.
These parameters show actual (non-adjustable)
values and can be used for monitoring and trouble-
shooting purposes.
) + 1'"" ! "
DRV-21 shows None
(VFD is ready) or the
current fault if VFD is tripped. It is possible to
check Hz, Amps, VFD mode and Trip time by
pressing [ENTER] key and then [UP] key for each
reading. When readings are checked, press
[ENTER] key to return to the fault display.
) +
"- !
' '
The Target value shows
what speed command
VFD should follow. The Output value shows the
actual VFD output speed. This parameter is very
useful for trouble-shooting.
) .+ $
> " !
!
8 9
When VFD runs in PID
mode the Reference is
the PID set-point (desired pressure, temperature
etc.) and Feedback is the actual process value read
from the transducer. The Target value shows what
speed command VFD should follow. This display is
DRV Jog Freq
16 10.00 Hz
DRV Fault
21 None
DRV TAR 35.00Hz
22 OUT 21.00Hz
DRV R 50.0PSI
22 F 28.0PSI
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......