Chapter 5 – Parameter List
5-3
CODE
Com.
Addr
Description
LCD Keypad
Display
Setting Range
Run
Adj.
Page
SET-65 9141 Speed VFD ramps down to when Aux starts MMC DecFreq
0 to FG1-30
SET-66 9142 MMC Feedback Start Differential
AuxStartDiff
0.0 to 100.0 [%]
SET-67 9143 MMC Feedback Stop Differential
AuxStopDiff
0.0 to 100.0 [%]
SET-74 914A Under/Over Level Detection Mode
Level Detect
0 (No)
6-8
1 (Under Level)
2 (Over Level)
SET-75 914B Level Detection Mode
Source
LDT Source
0 (Current)
1 (DC Voltage)
2 (Output Voltage)
3 (kW)
4 (V1)
5 (I)
SET-76 914C Level Detection Mode
Frequency
LDT Freq
0 to FG1-30 [Hz]
SET-77 914D Level Detection Mode
Delay Time
LDT Delay
0 to 9999 [sec]
SET-78 914E Level Detection Mode
Leve
l
LDT Level
0 to 999.9 [Unit]
SET-79 914F Level Detection Mode
Hysteresis
LDT Hyst
0 to 999.9 [Unit]
SET-80 9150 Level Detection mode Trip Setting
LDT Trip
0 (No)
1 (Yes)
SET-81 9151 Level Detection Mode
Well Fill Time
LDT FillTime
0 to 3000.0 [min]
SET-82 9152 Level Detection Mode
Output Relay
LDT Relay
0 None
1 AUX_3
2 AUX_4
SET-90 915A Local / Remote Key Operation Selection
LocalRemKey
0 (2nd Source)
1 (Cntl&RefStop)
2 (Control Stop)
3 (Ref Only)
4 (Cntl&Ref Run)
5 (Control Run)
6 (Disabled)
5.2 [SET] Parameter Group Default Settings
CODE
LCD Keypad
Display
Basic
Supply
Fan
Exhaust
Fan
Cooling
Tower
Circul.
Pump
Subm.
Pump
Vacuum
Pump
Const.
Torq.
SET-00 App. Select
Basic
Supp. Fan
Exh. Fan
Cooling T Circ.Pump Sub. Pump Vacuum
Const T
SET-01 Input Phase
3
3
3
3
3
3
3
3
SET-02 Motor HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
SET-03 Motor FLA
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
SET-04 Motor RPM
1800
1800
1800
1800
1800
3600
3600
1800
SET-06
Carrier Freq
(400-700HP)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
1.0kHz
(1.0kHz)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
SET-07
VAC 575.0V
VAC 480.0V
VAC240.0V
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
SET-08 Motor Volt
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
SET-09 Drive Mode
Remote1
Remote1
Remote1
Remote1
Remote1
Keypad
Remote1
Remote1
SET-10 Speed Ctrl
I
I
I
Keypad1
Keypad1
Keypad1
Keypad1
Keypad1
SET-11
ACC Time
(150-700HP)
20.0sec
(60.0sec)
20.0sec
(60.0sec)
20.0sec
(60.0sec)
20.0sec
(60.0sec)
20.0sec
(60.0sec)
2.0sec
30.0sec
(60.0sec)
20.0sec
(60.0sec)
SET-12
DEC Time
(150-700HP)
30.0sec
(90.0sec)
30.0sec
(90.0sec)
30.0sec
(90.0sec)
30.0sec
(90.0sec)
30.0sec
(90.0sec)
10.0sec
(20.0sec)
120.0sec
30.0sec
(90.0sec)
SET-13 Low Limit
20.00Hz
20.00Hz
20.00Hz
20.00Hz
30.00Hz
30.00Hz
30.00Hz
10.00Hz
SET-14 High Limit
60.00Hz
60.00Hz
60.00Hz
60.00Hz
60.00Hz
60.00Hz
60.00Hz
60.00Hz
SET-15 Run Prev.
Reverse
Reverse
Reverse
Reverse
Reverse
Reverse
Reverse
None
SET-16 Stop Mode
Coast
Coast
Coast
Coast
Decel
Decel
Coast
Decel
SET-20 PID Mode
No
No
No
Yes
Yes
Yes
Yes
No
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......