Chapter 6 - Parameter Description
6-33
6.6 Application Group [APP]
%
)**+ B'
1
APP-00
allows jumping
to any parameter in
APP group without scrolling to it. Press [ENTER]
key and input desired parameter code by using
[SHIFT] and [UP]/[DOWN] keys.
When [ENTER] key is pressed again, the desired
parameter will be on the display.
%
)* + $
8 9
F
APP-01
parameter sets
the PID Feedback
scaling percentage. The default setting is 100% and
it is optimal for most applications. If it is set to a
higher number, the PID control will be more
responsive but can be unstable.
%
)* + %':
"
> " !
APP-02
parameter
enables APP-03 and
auxiliary reference mode for PID control.
%
)*.+ %':
"
> " !
-!
!
APP-03
parameter has
nine selections for
auxiliary reference signal: Keypad-1, Keypad
Up/Down, V1, V1S, I, V1+I, Pulse, Int.485 and
Ext. PID. Refer to SET-10 parameter for detailed
description.
%
)*/A*0+ $
8 9
:
'
' > " $6
!
'
! '
One of these three PID Feedback Max. Value
parameters will be available when corresponding
input is selected in SET-21. The value can be set
from 0 to maximum SET-04, SET-09 or SET-15.
%
)*5+ $
" & &
! <
=
The Derivative
parameter of the PID
control allows creating an offset on the PID output
value based on rate of error change. In other words,
this parameter predicts a future error level and PID
adjusts its output to correct it.
%
) + $
' '
APP-12
setting
determines the PID
output scaling factor. The default is 100% and it is
optimal for most of the applications.
%
) .+ $
!
)
!
APP-13
setting
determines the PID
second P Gain value. The PID P gain will be
switched to P Gain 2 when digital input set to P-
Gain2 is activated. The default is 100%.
%
) /+ $
!
APP-14
setting
determines the PID P-
Gain and P Gain 2 scaling factor. The default is
100%.
%
) 3+ $
8 9
1'"&
!
APP-17
setting
switches the PID
feedback curve to U type. If VFD control is set to S
curve, the APP-17 can be set to Yes to match control
and feedback curves.
1
$
%
) *6 +
! %
!
The VFD will switch control to second settings
when digital input set to 2nd Function is activated.
APP-20-
The second acceleration time setting.
APP-21-
The second deceleration time setting.
APP Jump Code
00 40
APP AuxRef Mode
02 Yes
SET Aux Ref Sel
03 V1
APP PID D Time
09 0.0 sec
APP PID OutScale
12 100.0 %
APP PID P2 Gain
13 100.0 %
APP P GainScale
14 100.0 %
APP PID F Gain
01 100.0%
APP PIDFB I Max
04 20.00 mA
APP PIDFB V1 Max
05 10.0 V
APP PIDFB P Max
06 10.0 kHz
APP PID U Fbk
17 No
APP 2nd AccTime
20 5.0 sec
APP 2nd DecTime
21 10.0 sec
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......