Chapter 2 – Specification
2-5
Emergency Stop Immediately Interrupts the VFD Output in any control method
Jog
Jog Operation with adjustable Jog frequency
Fault Reset
Resets VFD. Some critical faults can only be reset by recycling the VFD power.
O
u
tp
u
t
si
g
n
al
s Four Multi-
Function Relays
Each relay can be set to Frequency Detection Level, Overload Alarm, Stalling,
Over Voltage, Low Voltage, VFD Overheating/ Running/ Stopping/ At Speed, VFD
By-Pass, Speed Search etc.
Fault Output
Double Throw Relay Contact (3A, 3C, 3B) – 1A up to 250VAC or 30VDC
Two Analog
Outputs
Selections: Output Frequency, Output Current, Output Voltage, Output kW, DC
Link Voltage. Both outputs are 0-10VDC scalable from 10 to 200%.
Operation Functions
DC Braking, Frequency Limit, Jump Frequencies, 2
nd
Function, Slip Compensation,
Reverse Rotation Prevention, Auto Restart, Auto-Tuning, PID Control,
Flying
Start, Safety Stop, Flux Braking, Low leakage, Pre-PID, Dual-PID, MMC
(4)
, Motor
Pre-heat.
P
R
O
T
E
C
T
IO
N
VFD Fault Trips
Over Voltage, Low Voltage, Over Current, Overload Protection, Short Circuit
Protection, Ground Fault, VFD Overheat, Motor Overheat, Output Phase Open,
External Trip, CPU Communication Error, Loss of Speed Command, Hardware
Fault, etc.
VFD Alarm
Stall Prevention, Overload Alarm, Thermal Sensor Fault
D
IS
P
L
A
Y
K
ey
p
ad
Operation
Information
Output Frequency, Output Current, Output Voltage, Frequency Set Value,
Operating Speed, DC Voltage,
kWattmeter, Run-time, Last Trip Time
Fault History
The VFD stores 5 last faults with Hz, A, VFD mode and trip time for each fault.
E
N
V
IR
O
N
M
E
N
T
Ambient Temperature 14°F~ 104
℉
(-10
℃
~ 40
℃
). De-rate VFD by 20% to increase rating up to 122
℉
Storage Temperature
-4°F~ 149
℉
(-20
℃
~ 65
℃
)
Ambient Humidity
Up to 95 % RH. (Non-Condensing)
Altitude
Max. 3,300ft (1,000m). De-rate VFD 20% for every additional 1000ft.
Vibration
Max. 0.6g (5.9m/sec
2
)
Environmental
Conditions
Pollution degree 2. No Corrosive Gas, Combustible Gas, Oil Mist or Dust
Notes:
1)
Standard duty VT motor rating based on a 110% overload for 1 minute. Heavy-duty VT or Standard Duty CT
motor ratings based on 150% overload for 1 minute. The motor horsepower ratings are based on VFD nominal
voltage and 4-pole motor design. Operation at lower input voltages or motors with six or more motor poles
may require to upsize the drive depending on actual motor FLA rating.
2)
Output voltage cannot exceed the input voltage. An output voltage should be programmed in the range from
input voltage to a minimum of the VFD voltage rating.
3)
The standard conduit box attachment adds 1.8kg (4 lbs.), as minimum, to the weight of the drive.
4)
MMC (Multi Motor Control) function is not available for 150HP and above VFDs.
5)
De-rate VFD by 50% when the single-phase power will be applied to the VFD.
6)
UL Open Type VFD with installed UL Type 1 kit.
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......