Chapter 10 – Modbus-RTU Communication
10-4
Address
Parameter
Unit
Unit R/W
Data value
BIT13: REM. R/S (Int. 485, OPT)
BIT14: REM. Freq. (Int. 485, OPT)
0x000F Trip information
R
BIT 0 : OCT1
BIT 1 : OV
BIT 2 : EXT-A
BIT 3 : BX
BIT 4 : LV
BIT 5 : RESERVE
BIT 6 : GF(Ground Fault)
BIT 6: OHT (VFD overheat)
BIT 7: ETH (Motor overheat)
BIT 8: OLT (Overload trip)
BIT10: HW-Diag
BIT11: RESERVE
BIT12: OCT2
BIT13: OPT (Option error)
BIT14 : PO (Phase Open)
BIT15: IOLT
0x0010 Input terminal status
R
BIT 0 : M1
BIT 1 : M2
BIT 2 : M3
BIT 3 : M4
BIT 4 : M5
BIT 5 : M6
BIT 6 : M7
BIT 7 : M8
BIT 8 : RESERVED
BIT 9 : RESERVED
BIT 10 : RESERVED
0x0011 Output terminal status
R
BIT 0 : AUX1
BIT 1 : AUX2
BIT 2 : AUX3
BIT 3 : AUX4
BIT 4 : RESERVED
BIT 5 : RESERVED
BIT 6 : RESERVED
BIT 7 : 30AC
0x0012
V1
0~10V
R
0x0013
V2
0~10V
R
0x0014
I
0~20mA
R
0x0015
RPM
R
0x001A
Unit display
R 0 : Hz, 1 : Rpm
0x001B
Pole number
R
0x001C
Custom Version
R
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......