Chapter 5 – Parameter List
4-2
4.1.2 Display Description
Displays
Description
1) Parameter Group
Displays the current parameter group. Parameter groups include: SET, DRV,
FG1, FG2, I/O, EXT, COM and APP.
2) Start/Stop Source
Displays the source of VFD Start and Stop command.
K
: Keypad control. Start/Stop command from FWD or REV keys on the keypad
T
: Terminal Control. Start/Stop command from VFD digital inputs FX or RX
R
: Communication control. Start/Stop command from VFD RS485 port
O
: Option Board Control. Start/Stop from option communication board
3) Frequency Setting
Source
Displays the source of VFD frequency reference command
K
: Frequency reference from keypad
V
: Frequency reference 0-10VDC from V1 analog input
W
: Frequency reference ±10VDC from V1S analog input
I:
Frequency reference 4-20mA from I analog input
P
: Frequency reference from A0-B0 Pulse Frequency input
R
: Frequency reference from RS485 port
U
: Up terminal input when Up/Down operation is selected
D
: Down terminal input when Up/Down operation is selected
S
: Stop status when Up/Down operation is selected
O
: Frequency reference from option communication board
X
: Frequency reference from Sub board
J
: Jog Frequency reference from Jog input
1 ~ 15
: Number of activated by digital input Step frequency
4) Output Current*
Displays the actual Output (motor) Current during operation.
5) Parameter Code
Displays two-digit parameter number (0-99) and letter
L
when VFD is in local
control mode. Use the
(Up),
(Down) key to cycle through parameters.
6) Operating Status
Displays the operation information.
STP
: Stop
FWD
: During Forward operation
REV
: During Reverse operation
DCB
: During DC Braking mode
LOP
: Loss of Reference from Option Board (DPRAM fault)
LOR
: Loss of Reference from Option Board (Communication network fault)
LOV
: Loss of 0-10VDC Analog Frequency Reference on V1 input
LOI
: Loss of 4-20mA Analog Frequency Reference on I input
LOS
: Loss of Reference from Sub-Board
7) VFD Output or
Command Frequency
Displays the Output Frequency during run.
Displays the Command Frequency during stop.
* The VFD diplays a true value of a motor current measured by Hall effect current sensors. The most of the current
clamp meters have inductive current sensors and cannot properly read a VFD output current with high frequency
components.
) *
*
*
) (
*
*
+) ,
-)
,
(
" .
(
*
/) ,
*
0) 1
2
3) 1
"'
▶
4
5 5 6
55
* 1 /5 5578
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......