Chapter 5 – Parameter List
5-1
CHAPTER 5 -
PARAMETER LIST
5.1 [SET] Setup Parameter Group
The parameter codes in gray are hidden until the corresponding feature parameter in bold is activated.
The parameters marked with can be changed during run and with in stop mode only.
CODE
Com.
Addr
Description
LCD Keypad
Display
Setting Range
Run
Adj.
Page
SET-00 9100 Application Selection
App. Select
none
6-1
Basic
Supp Fan
Exh Fan
Cooling Twr
Circ Pump
Subm. Pump
Vacuum
Const Trq
SET-01 9101 3-phase or Single phase power
Input Phase
1-Phase
3-phase
SET-02 9102 Rated Motor HP
Motor HP
0.5~700 HP
6-2
SET-03 9103 Rated Motor Current
Motor FLA
1.0~999.9A
SET-04 9104 Rated Motor Synchronous RPM
Motor RPM
60Hz
= 600, 720, 900,
1200, 1800, 3600
50Hz
= 500, 600, 750,
1000, 1500, 3000
SET-06 9106 Carrier Frequency
Carrier Freq
0.7 ~15.0kHz
40HP = ~10.0kHz
50~100HP = ~ 4.0kHz
125~ 400HP= ~ 3.0kHz
500HP~ = ~ 2.0kHz
SET-07 9107 Input voltage adjustment
VAC575.0V
VAC 440.0
VAC 220.0
77.6~115 [%]
73 to 115.0 [%]
73 to 115.0 [%]
SET-08 9108 Motor Rated Voltage
Motor Volt
0 to 600 [V]
SET-09 9109 Run/Stop Method
Drive Mode
0 (Keypad)
1 (Remote-1)
2 (Remote-2)
3 (Int. 485)
SET-10 910A Speed Control Reference
Speed Ctrl
0 (Keypad-1)
1 (Keypad-Up/Dwn)
2 (V1)
3 (V1S)
4 (I)
5 (V1+I)
6 (Pulse)
7 (Int. 485)
8 (Ext. PID)
SET-11 910B Acceleration Time
ACC Time
0 to 600.0 [sec]
6-4
SET-12 910C Deceleration Time
DEC Time
0 to 600.0 [sec]
SET-13 910D V/F Frequency
LowLimit
Low Limit
0.00 to SET-14
6-4
SET-14 910E V/F Frequency
High Limit
High Limit
SET-13 to FG1-30
SET-15 910F Run Prevention
Run Prev.
0 (None)
1 (Forward Prev)
2 (Reverse Prev)
SET-16 9110 Stop Mode
Stop Mode
0 (Decel)
1 (Dc-brake)
2 (Coast)
3 (Flux-brake)
SET-20 9114 PID Operation Selection
PID Mode
0 (No)
6-4
7-1
1 (Yes)
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......