![CERUS CI-007-P2 Installation, Programming Operation, & Maintenance Manual Download Page 50](http://html1.mh-extra.com/html/cerus/ci-007-p2/ci-007-p2_installation-programming-operation-and-maintenance-manual_2583979050.webp)
Chapter 5 – Parameter List
5-7
5.5 [FG1] Function Group 1 parameter group
CODE
Com.
Addr
Description
LCD Keypad
Display
Setting Range
Adjust
Run
Page
FG1-00
9300
Jump to Desired Code #
Jump Code
1 to 91
6-12
FG1-01
9302
Acceleration Pattern
Acc. Pattern
0 (Linear)
1 (S-curve)
2 (U-curve)
FG1-02
9303
Deceleration Pattern
Dec. Pattern
0 (Linear)
1 (S-curve)
2 (U-curve)
FG1-03 9304
Accel. S-Curve Ratio
Start Curve
0 to 100 [%]
FG1-04
9305
Decel. S-Curve Ratio
End Curve
0 to 100 [%]
FG1-10
930A
Pre-Heat
PreHeat Mode
0 (No)
1 (Yes)
FG1-11
930B
Pre-Heat Value
PreHeatLevel
1 to 50 [%]
6-13
FG1-12
930C
Pre-Heat Duty Cycle
PreHeatDuty
1 to 100 [%]
FG1-20
9314
Start Mode
Start Mode
0 (Accel)
1 (Dc-start)
2 (Flying-start)
FG1-21 9315
DC Injection Start
Time
DcSt Time
0.0 to 60.0 [sec]
FG1-22
9316
DC Injection Start
Value
DcSt Value
0 to 150 [%]
FG1-24
9318
DC Injection Braking
On-delay
DcBr Delay
0.00 to 60.00 [sec]
FG1-25
9319
DC Injection Braking
Frequency
DcBr Freq
0.01 to 60.00 [Hz]
FG1-26
931A
DC Injection Braking
Time
DcBr Time
1.0 to 60.0 [sec]
FG1-27
931B
DC Injection Braking
Value
DcBr Value
0 to 200 [%]
FG1-28
931C
Safety Stop
Safety Stop
0 (No)
6-14
1 (Yes)
FG1-29
931D
Power Source Freq
Line Freq
40 to 120 [Hz]
FG1-30
931E
Maximum Frequency
Max Freq
40 to 120 [Hz]
FG1-31
931F
Base Frequency
Base Freq
30 to 120 [Hz]
FG1-32
9320
Starting Frequency
Start Freq
0.01 to 10.00 [Hz]
FG1-40
9328
Volts/Hz Pattern
V/F Pattern
0 (Linear)
1 (Square)
2 (User V/F)
FG1-41
9329
User V/F - Frequency 1
User Freq 1
0 to FG1-30
FG1-42
932A
User V/F - Voltage 1
User Volt 1
0 to 100 [%]
FG1-43
932B
User V/F - Frequency 2
User Freq 2
0.00 to FG1-30
FG1-44
932C
User V/F - Voltage 2
User Volt 2
0 to 100 [%]
FG1-45
932D
User V/F - Frequency 3
User Freq 3
0.00 to FG1-30
FG1-46
932E
User V/F - Voltage 3
User Volt 3
0 to 100 [%]
FG1-47
932F
User V/F - Frequency 4
User Freq 4
0.00 to FG1-30
FG1-48
9330
User V/F - Voltage 4
User Volt 4
0 to 100 [%]
FG1-51
9333
Energy Save
Energy Save
0 (None)
6-15
1 (Manual)
2 (Auto)
FG1-52 9334
Energy Save %
Manual Save%
0 to 30 [%]
FG1-54
9336
Integrating Wattmeter
KiloWattHour
M kWh
Display
FG1-55
9337
Inverter Temperature
Inv. Temp.
0 to 160 [°C]
FG1-56
9338
Motor Temperature
Motor Temp.
0 to 160 [°C]
FG1-57
9339
No Motor Trip Selection
No Motor Sel
0 (No)
6-15
1 (Yes)
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......