Chapter 5 – Parameter List
5-2
CODE
Com.
Addr
Description
LCD Keypad
Display
Setting Range
Run
Adj.
Page
SET-21 9115 PID Feedback Signal
PID F/B
0 (I)
6-4
1 (V1)
2 (Pulse)
SET-22 9116 Feedback Unit Select
F/B Unit
0 (PSI)
1 (°F)
2 (°C)
3 (inWC)
4 (inM)
5 (Bar)
6 (mBar)
7 (Pa)
8 (kPa)
9 (CUST)
SET-23 9117 PID Unit Format
Unit Format
0 0.01
6-5
1 0.1
SET-25 9119 Feedback Unit Maximum Value
F/B Unit Max
0 to 3000.0 [Unit]
SET-26 911A PID Set Point Value
PID SetPoint
0 to SET-25 [Unit]
SET-27 911B PID Frequency Low Limit
PID Limit-L
FG1-32 to SET-28 [Hz
]
SET-28 911C PID Frequency High Limit
PID Limit-H
SET-27 to FG1-30
SET-29 911D P Gain for PID Control
PID P Gain
0.0 to 999.9 [%]
SET-30 911E I Gain for PID Control
PID I Time
0.0 to 32.0 [sec]
SET-31 911F PID Output Inverse
Out Inverse
0 (No)
1 (Yes)
SET-32 9120 Sleep Mode Frequency
Sleep Freq
0.00 to SET-23 [Hz]
6-5
7-2
SET-33 9121 Sleep Mode
Delay Time
Sleep Delay
0 to 9999 [sec]
SET-34 9122 Sleep Mode
Boost Value
Sleep Boost
0 to 3000.0 [Unit]
SET-35 9123 Sleep Mode
Wake-Up Level
WakeUp Level
0.0 to 100.0 [%]
SET-36 9124 PrePID Reference Frequency
PrePID Freq
0.00 to FG1-30 [Hz]
6-6
7-4
SET-37 9125 PrePID
Stop delay
PrePID Dly
0 to 9999.0 [sec]
SET-38 9126 PrePID
Exit Level
PrePID Exit
0 to 3000.0 [Unit]
SET-40 9128 Pipe Broken Mode Selection
PBrokenMode
0 (No)
6-6
7-3
1 (Yes)
SET-41 9129 Pipe Broken Mode
Frequency
PBrokenFreq
0.00 to FG1-30 [Hz]
SET-42 912A Pipe Broken Mode
Delay Time
PBrokenDly
0 to 9999.0 [sec]
SET-43 912B Pipe Broken Mode
Feedback Level
PBroken F/B
0 to 3000.0 [Unit]
SET-44 912C Pipe Broken Mode
Output Relay
PBrokenRelay
0 None
1 AUX_3
2 AUX_4
SET-50 9132 MMC / Lead-Lag Operation
MMC Mode
0 (No)
6-6
1 (Yes)
SET-51 9133 Number of Auxiliary Motors in Use
Nbr Aux's
0 to 4
SET-52 9134 Start Frequency of Aux. Motor 1
Start Freq 2
0 to FG1-30 [Hz]
6-7
SET-53 9135 Start Frequency of Aux. Motor 2
Start Freq 2
SET-54 9136 Start Frequency of Aux. Motor 3
Start Freq 3
SET-55 9137 Start Frequency of Aux. Motor 4
Start Freq 4
SET-56 9138 Stop Frequency of Aux. Motor 1
Stop Freq 1
SET-57 9139 Stop Frequency of Aux. Motor 2
Stop Freq 2
SET-58 913A Stop Frequency of Aux. Motor 3
Stop Freq 3
SET-59 913B Stop Frequency of Aux. Motor 4
Stop Freq 4
SET-60 913C Delay Time before Aux Motor Start
Aux Start DT
0.0 to 999.9 [sec]
SET-61 913D Delay Time before Aux Motor Stop
Aux Stop DT
0.0 to 999.9 [sec]
SET-62 913E Accel time when Aux motor stops
MMC AccTime
0 to 600.0 [sec]
SET-63 913F Speed VFD ramps up to when Aux stops
MMC AccFreq
0.00 to FG1-30 [Hz]
SET-64 9140 Decel time when Aux motor starts
MMC DecTime
0 to 600.0 [sec]
6-7
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......