Chapter 5 – Parameter List
5-19
5.11 [APP] Application parameter group
CODE
Comm.
Addr
Description
LCD Keypad
Display
Setting Range
Run
Adj.
Page
APP-00
9600
Jump to Desired Code #
Jump Code
1 to 78
6-33
APP-01
9601
PID F Gain Selection
PID F Gain
0 to 999.9[%]
APP-02 9602
PID Auxiliary Reference Mode
Selection
Aux Ref Mode
0 (No)
1 (Yes)
APP-03 9603
PID Auxiliary Reference Signal
Selection
Aux Ref Sel
0 (Keypad-1)
1 (Keypad-2)
2 (V1)
3 (V1S)
4 (I)
5 (V1+I)
6 (Pulse)
7 (Int. 485)
8 (Ext. PID)
APP-04
9604
PID Feedback I Max Limit
PIDFB I Max
0.00 to 20.00mA
APP-05
9605
PID Feedback V1 Max Limit
PIDFB V1 Max
0.00 to 12.00V
APP-06
9606
PID Feedback Pulse Max Limit
PIDFB P Max
0.0 to 100.0kHz
APP-09
9609
D Gain for PID Control
PID D Time
0.0 to100.0 [msec]
APP-12
960C
PID Output Scale
PID OutScale
0.0 to 999.9 [%]
APP-13
960D
PID P2 Gain
PID P2 Gain
0.0 to 999.9 [%]
APP-14
960E
P Gain Scale
P Gain Scale
0.0 to 100.0 [%]
APP-17
9611
PID U curve feedback select
PID U Fbk
0 (No)
1 (Yes)
APP-20 9614
2nd Acceleration Time
2nd Acc Time
0 to 6000 [sec]
APP-21
9615
2nd Deceleration Time
2nd Dec Time
0 to 6000 [sec]
APP-22
9616
2nd Base Frequency
2nd BaseFreq
30.00 to FG1-30 [Hz]
6-34
APP-23
9617
2nd V/F Pattern
2nd V/F
0 (Linear)
1 (Square)
2 (User V/F)
APP-24
9618
2nd Forward Torque Boost
2nd F Boost
0.0 to 15.0 [%]
APP-25
9619
2nd Reverse Torque Boost
2nd R Boost
0.0 to 15.0 [%]
APP-26
961A
2nd Stall Prevention Level
2nd Stall
30 to 150 [%]
APP-27
961B
2nd Electronic Thermal Level for 1
minute
2nd ETH 1min
APP-28 to 200 [%]
APP-28
961C
2nd Electronic Thermal Level for
continuous
2nd ETH Cont
50 to 150%
APP-29
961D
2nd Rated Motor Current
2nd R Curr
1.0~999.9A
APP-40
9628
Number of Running Auxiliary
Motors Display
Aux Mot Run
*
Display
APP-41
9629
Aux. Motor Start Selection
Starting Aux
1 to 4
APP-42
962A
Auto Alternation Time Display
Auto Op Time
*
Display
APP-44
962C
Aux motor First-In and Last-Out
F-in L-out
0 (No)
1 (Yes)
APP-45
962D
All Aux. motors Simultaneous Stop All Stop
0 (No)
1 (Yes)
APP-66
9642
Auto Change Mode Selection
AutoCh Mode
0 (None)
1 (Aux)
2 (Main)
APP-67
9643
Auto Change Time
AutoEx Intv
00:00 to 99:00 (h)
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......