Chapter 3 – Installation & Wiring
3-8
3.2.7 Wire sizes and terminal lugs
Refer to below table for recommended wires sizes, terminal lugs, and screws for VFD power and motor
wiring.
VFD capacity
HP (
kW
)
S
c
re
w
S
iz
e
M
e
tr
ic
Screw Torque
Wire size
R
(L1)
, S
(L2)
, T
(L3)
U, V, W
kgf · cm
lb · in
mm
2
AWG
or
kcmil
mm
2
AWG
or
kcmil
2
3
0
V
A
C
7.5HP
(5.5kW)
M4
7.1 ~ 12.2
6.2~10.6
5.5
10
5.5
10
10HP
(7.5kW)
M5
24.5 ~ 31.8
21.2~27.6
8
8
8
8
15HP
(11kW)
M5
14
6
14
6
20HP
(15kW)
M6
30.6 ~ 38.2
26.6~33.2
22
4
22
4
25HP
(18.5kW)
M6
38
2
38
2
30HP
(22kW)
M8
61.2 ~ 91.8
53.1~79.7
38
2
38
2
40HP
(30kW)
M8
60
1/0
60
1/0
4
6
0
V
A
C
7.5HP
(5.5kW)
M4
7.1 ~ 12.2
6.2~10.6
3.5
12
3.5
12
10HP
(7.5kW)
15HP
(11 kW)
5.5
10
5.5
10
20HP
(15kW)
M6
30.6~38.2
26.6~33.2
8
8
8
8
25HP
(18.5kW)
14
6
14
6
30~40HP
(22~30kW)
M8
61.2~91.8
53.1~79.7
22
4
22
4
50~75HP
(37~55kW)
67.3~87.5
58.4~75.9
38
2
38
2
100~125HP
(75~90kW)
M10
89.7~122.0
77.9~105.9
60
1/0
60
1/0
150~200HP
(110~132kW)
M12
182.4~
215.0
158.3~
186.6
100
4/0
100
4/0
250HP
(160kW)
150
300
150
300
350HP
(220kW)
200
400
200
400
400HP
(280kW)
250
500
250
500
500HP
(315kW)
325
700
325
700
600HP
(375kW)
2x200
2x400
2x200
2x400
700HP
(450kW)
2x250
2x500
2x250
2x500
6
0
0
V
A
C
7.5HP
(5.5kW)
M4
7.1 ~ 12.2
6.2~10.6
3.5
12
3.5
12
10HP
(7.5kW)
15HP
(11kW)
5.5
10
5.5
10
20HP
(15kW)
M6
30.6~38.2
26.6~33.2
8
8
8
8
25HP
(18.5kW)
14
6
14
6
30~40HP
(22~30kW)
M8
61.2~91.8
53.1~79.7
22
4
22
4
50~75HP
(37~55kW)
38
2
38
2
100~125HP
(75~90kW)
M10
89.7~122
77.9~105.9
60
1/0
60
1/0
150~200HP
(110~132kW)
M12
182.4~215
158.3~186.6
100
4/0
100
4/0
Notes: Apply the rated torque to terminal screws providing proper wire connection and protecting the thread from
damage. Loose screws can cause VFD malfunction or damage. Use copper wires with 600V, 75°C ratings. For
10~15HP (7.5~11kW) 230V type VFDs the power and motor terminals are only for use with insulated ring type
connectors.
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......