Chapter 5 – Parameter List
4-8
4.3.8 Saving and Resetting Parameters
Parameter Name
Code
Description (Default Value)
Para. Read
FG2-91
Reads parameters from VFD and saves to a keypad memory (No)
Para. Write
FG2-92
Writes parameters from keypad memory to VFD memory (No)
Para. Init.
FG2-93
Initializes either all program groups or selected one (No)
Para. Save
FG2-95
Saves parameters permanently to VFD memory (No)
Note: All these parameters work only in VFD stop mode. It is recommended to save current parameters to a keypad
before initializing VFD during trouble-shooting. This way the VFD can be returned to current state at any point.
4.3.9 Auto start parameters
Parameters for VFD auto start in different conditions
Parameter Name
Code
Description (Default Value)
Power On Run
FG2-19
VFD auto starts after power up with present run command (Yes)
RST Restart
FG2-21
VFD auto starts after fault reset with present run command (Yes)
IPF Mode
FG2-22
VFD auto starts after Instantaneous Power Failure (Yes)
4.3.10 Control Methods and Patterns
Parameter Name
Code
Description (Default Value)
Stop Mode
SET-16
Four Stop Modes: Decel, DC-Brake, Cost, Flux Brake (Decel)
PID Mode
SET-20
Proportional-Integral control mode (No)
MMC Mode
SET-50
Starts Auxiliary Motors at High Demand (No)
Acc. Pattern
FG1-01
Acceleration curves: Linear, S-curve, U-curve (Linear)
Dec. Pattern
FG1-02
Deceleration curves: Linear, S-curve, U-curve (Linear)
PreHeat Mode
FG1-10
Provides Motor Winding Preheat in VFD stop mode (No)
Start Mode
FG1-20
Three Start Modes: Accel, DC-Start, Flying Start (Accel)
Safety Stop
FG1-28
During Power loss VFD decelerates using load inertia (No)
V/F Pattern
FG1-40
Three Patterns: Linear, Square, User V/F (Linear)
Energy Save
FG1-51
Decreases output voltage at steady speed to save energy. (None)
Control Mode
FG2-60
Three modes: V/F, Sleep Compensation, Sensorless (V/F)
Torque Boost
FG2-67
Provides initial voltage at start for torque boost (Manual)
4.4 Control Wiring Configurations
4.4.1 Examples of digital control configurations
The 4.4.1 picture shows four most common control configurations.
Config. #1
shows VFD controlled by separate Forward and Reverse inputs when SET-09 parameter is set to
Remote-1 mode. If both inputs are activated simultaneously, the VFD will stop.
Config. #2
shows VFD controlled by Run and Forward/Reverse inputs when SET-09 parameter is set to
Remote-2 mode. Forward Run mode is activated by Run input and Reverse mode by both Run and Fwd/Rev
inputs.
Config. #3
shows VFD controlled by Start/Stop momentary push buttons when SET-09 parameter is set to
Remote-1 mode and M3 input to 3-Wire. When Start button is pressed, the VFD starts Forward. The VFD
stops when Stop button is pressed.
Config. #4
shows 2-Speed VFD control. Parameter SET-09 is set to Remote-1 mode and SET-10 to
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......