Chapter 5 – Parameter List
5-15
CODE
Comm.
Addr
Description
LCD Keypad
Display
Setting Range
Run
Adj.
Page
I/O-55
9537
Deceleration Time 3
Dec Time-3
I/O-56
9538
Acceleration Time 4
Acc Time-4
I/O-57
9539
Deceleration Time 4
Dec Time-4
I/O-58
953A
Acceleration Time 5
Acc Time-5
I/O-59
953B
Deceleration Time 5
Dec Time-5
I/O-60
953C
Acceleration Time 6
Acc Time-6
I/O-61
953D
Deceleration Time 6
Dec Time-6
I/O-62
953E
Acceleration Time 7
Acc Time-7
I/O-63
953F
Deceleration Time 7
Dec Time-7
I/O-68
9544
Damper or Lubrication Mode
Dmpr LubeSel
0 (None)
6-27
1 (Damper)
2 (Lubrication)
I/O-69
9545
Damper/Lubrication Relay Timer
Dmpr/LubeTmr
0 to 6000 [sec]
I/O-70
9546
S0 Output Selection
S0 Mode
0 (Frequency)
1 (Current)
2 (Voltage)
3 (kW)
4 (Ext PID Out)
I/O-71
9547
S0 Output Scale
S0 Adjust
10 to 200 [%]
I/O-72
9548
S1 Output Selection
S1 Mode
Same as I/O-70
I/O-73
9549
S1 Output Scale
S1 Adjust
10 to 200 [%]
I/O-74
954A
Frequency Detection Level
FDT Freq
0.00 to FG1-30 [Hz]
6-28
I/O-75
954B
Frequency Detection Bandwidth
FDT Band
0.00 to FG1-30 [Hz]
I/O-76
954C
Programmable Digital Auxiliary
Relay1 Define
(A1-C1)
Aux Relay1
0 (NONE)
1 (FDT-1)
2 (FDT-2)
3 (FDT-3)
4 (FDT-4)
5 (FDT-5)
6 (OL)
7 (IOL)
8 (Stall)
9 (OV)
10 (LV)
11 (OH)
12 (Lost Command)
13 (RUN)
14 (STOP)
15 (Steady)
16 (INV Line)
17 (COMM Line)
18 (SpeedSearch)
19 (Ready)
20 (MMC)
21 (Local)
22 (Remote)
23 (PIPE BROKEN)
24 (DAMPER)
25 (LUBRICATION)
26 (LEVEL DETECT)
Summary of Contents for CI-007-P2
Page 23: ......
Page 107: ......
Page 110: ...Chapter 6 Parameter Description 7 4 PID control with Pipe Broken function diagram...
Page 111: ...Chapter 6 Parameter Description 7 4 7 5 PID control with Pre PID function diagram...
Page 112: ...Chapter 6 Parameter Description 7 5 7 6 PID Control Setting Notes...
Page 113: ......