7–103
62-11640
07001
ECONOMIZER PRESS SENSOR
• ACTIVATION: Economizer Pressure (ECOP) sensor is out of range.
• UNIT CONTROL: Engine and Electric: Alarm only. Economizer forced to STANDARD mode when alarm
is active.
• RESET CONDITION: Economizer Pressure sensor is in range or alarm may be manually reset using the
display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in
Section, page 7-2.) Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check System Pressures
Check Unit Data. Refer to
. Compare the pressure readings for the ECOP, the CSP and
the CDP. The ECOP should read between the CSP and the CDP, if not it indicates the ECOP has
failed. Refer to
for instruction on comparison. If discharge pressure is in normal
range, proceed to next step.
Place the Unit in Service Mode. Refer to
. After the unit has equalized, compare the
pressure readings for the ECOP, the CSP and the CDP. The ECOP the CSP and the CDP should all
read within 5 PSI, if not it indicates the ECOP has failed. Refer to
comparison.
2.
Check Economizer Pressure Sensor
Inspect sensor & connectors. Verify there is no damage to sensor, and no damage, moisture, or cor-
rosion in connectors.
07006
SUCTION PRESSURE SENSOR
• ACTIVATION: Suction pressure sensor is out of range. If Economizer pressure < or = (Suction pressure
−
10) for 10 seconds and suction pressure is > than 40 psig and < than 60 psig with the compressor running.
• UNIT CONTROL: Engine and Electric: Alarm only. Economizer forced to STANDARD mode when alarm
is active.
• RESET CONDITION: Auto reset when Suction Pressure Sensor is in range or, alarm may be manually
reset using the display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check System Pressures
Check Unit Data. Refer to
. Compare the pressure readings for the ECOP, the CSP and
the CDP. The ECOP should read between the CSP and the CDP. Refer to
tion on comparison. If pressures are in normal range, proceed to next step.
Place the Unit in Service Mode. Refer to
. After the unit has equalized, compare the pres-
sure readings for the ECOP, the CSP and the CDP. The ECOP the CSP and the CDP should all read
within 5 PSI, if not it indicates a failed sensor. Refer to
for instruction on comparison.
2.
Check Pressure Sensor
Inspect sensor & connectors. Verify there is no damage to sensor, and no damage, moisture, or cor-
rosion in connectors.
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......