7–63
62-11640
P00162
CHECK AFA SOLENOID CIRCUIT
• ACTIVATION: The (AFAR) circuit current draw is outside the normal range.
• UNIT CONTROL: Engine and Electric Operation: Pretrip will fail and display “PRETRIP FAIL AND COM-
PLETED”.
• RESET CONDITION: Auto reset if Pretrip is started again, or alarm may be manually reset using the dis-
play mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (Refer to Note 1 in
Section, page 7-2.) Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check relay operation
Refer to procedure for alarm
00090 CHK AFA SOLENOID CIRCUIT
. Alarm condition must be cor-
rected and the alarm cleared to continue.
P00170
CHECK LIV CIRCUIT
• ACTIVATION: During Test #2 the LIV current draw is not in range.
• UNIT CONTROL: Engine and Electric Operation: Alarm Only.
• RESET CONDITION: Auto Reset if Pretrip is started again, or alarm may be manually reset via keypad or
by turning the unit off, then back on again.
CORRECTIVE ACTIONS:
1.
Check LIV Circuit
Refer to procedure for alarm
P00173
CHECK ECONOMIZER
• ACTIVATION: Test #12, Check Economizer Expansion Valve fails.
• UNIT CONTROL: Engine and Electric Operation: Alarm Only.
• RESET CONDITION: Auto reset if Pretrip is started again or alarm may be manually reset using the dis-
play mounted keys or by turning the unit off then back on again.
CORRECTIVE ACTIONS:
1.
Check Economizer
Refer to procedure for alarm
& alarm
Summary of Contents for Vector 8500
Page 23: ...62 11640 1 6 1 3 SAFETY DECALS ...
Page 24: ...1 7 62 11640 62 03958 ...
Page 25: ...62 11640 1 8 ...
Page 26: ...1 9 62 11640 ...
Page 27: ...62 11640 1 10 ...
Page 125: ...62 11640 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 321: ......
Page 322: ......